Commissioning
4.2 Preparing for commissioning
Frequency inverters with Control Units CU230P-2 HVAC, CU230P-2 DP, CU230P-2 CAN
Operating Instructions, 01/2011, FW 4.4, A5E02430659B AD
57
NOTICE
Information about installation
The rating plate data that you enter must correspond to the connection type of the motor
(star connection [Y]/delta connection [Δ]), i.e. for a delta motor connection, the delta rating
plate data must be entered.
In which region of the world is the motor used? - Motor standard [P0100]
●
Europe IEC: 50 Hz [kW] - factory setting
●
North America NEMA: 60 Hz [hp] or 60 Hz [kW]
What is the prevailing temperature where the motor is operated? [P0625]
●
Motor ambient temperature [P0625], if it differs from the factory setting = 20° C.