Technical data
10.2 Technical data, Power Modules
Frequency inverters with Control Units CU230P-2 HVAC, CU230P-2 DP, CU230P-2 CAN
316
Operating Instructions, 01/2011, FW 4.4, A5E02430659B AD
Table 10- 16 PM240 frame size F, 3-ph. 380 V AC… 480 V, ± 10 %
Order number
with filter
without filter
6SL3224-0BE34-5AA0
6SL3224-0BE34-5UA0
6SL3224-0BE35-5AA0
6SL3224-0BE35-5UA0
6SL3224-0BE37-5AA0
6SL3224-0BE37-5UA0
Values based on Low Overload
● LO power
● LO input current
● LO output current
55 kW
129 A
110 A
75 kW
168 A
145 A
90 kW
204 A
178 A
Values based on High Overload
● HO power
● HO input current
● HO output current
45 kW
108 A
90 A
55 kW
132 A
110 A
75 kW
169 A
145 A
General values
● Power loss
● Fuse
● Cooling air requirement
● Cable cross-section for line and
motor connection
● Torque for line and motor and
motor connection
● Weight with filter
● Weight without filter
1.5 kW
160 A
150 l/s
35 … 120 mm
2
13 Nm
52 kg
36 kg
2.0 kW
200 A
150 l/s
35 … 120 mm
2
13 Nm
52 kg
36 kg
2.4 kW
250 A
150 l/s
35 … 120 mm
2
13 Nm
52 kg
36 kg
Table 10- 17 PM240 frame size F, 3-ph. 380 V AC… 480 V, ± 10 %
Order number
Without filter
6SL3224-0BE38-8UA0
6SL3224-0BE41-1UA0
Values based on Low Overload
● LO power
● LO input current
● LO output current
110 kW
234 A
205 A
132 kW
284 A
250 A
Values based on High Overload
● HO power
● HO input current
● HO output current
90 kW
205 A
178 A
110 kW
235 A
205 A
General values
● Power loss
● Fuse
● Cooling air requirement
● Cable cross-section for line and
motor connection
● Torque for line and motor and
motor connection
● Weight
2.4 kW
250 A
150 l/s
35 … 120 mm
2
13 Nm
39 kg
2.5 kW
315 A
150 l/s
35 … 120 mm
2
13 Nm
39 kg
Содержание SINAMICS G120 CU230P-2