Adapting the terminal strip
5.4 Analog inputs
Frequency inverters with Control Units CU230P-2 HVAC, CU230P-2 DP, CU230P-2 CAN
92
Operating Instructions, 01/2011, FW 4.4, A5E02430659B AD
Define the significance of the analog input
You define the analog input function by interconnecting a connector input of your choice with
parameter p0755. Parameter p0755 is assigned to the particular analog input via its index,
e.g. parameter p0755[0] is assigned to analog input 0.
Table 5- 6
Connector inputs (CI) of the inverter (selection)
CI
Significance
CI
Significance
p1070 Main setpoint
p1522 Torque limit, upper
p1075 Supplementary setpoint
p2253 Technology controller setpoint 1
p1503 Torque setpoint
p2264 Technology controller actual value
p1511 Supplementary torque 1
A complete list of the connector inputs is provided in the List Manual.
Table 5- 7
Example:
$,
r0755
755.0
p2253
Analog input 0 is the source for the speed setpoint.
Advanced settings
When required, you can smooth the signal, which you read-in via an analog input, using
parameter p0753.
For more information, see the parameter list and in the function block diagrams 9566 ff of the
List Manual.