Configuring the fieldbus
6.2 Communication via RS485
Frequency inverters with Control Units CU230P-2 HVAC, CU230P-2 DP, CU230P-2 CAN
148
Operating Instructions, 01/2011, FW 4.4, A5E02430659B AD
Table 6- 40 Binary input objects
Instance ID Object name
Description
Possible
values
Text active /
text inactive
Access type Parameter
BI0
DI0 ACT
State of DI 0
ON/OFF
ON/OFF
R
r0722.0
BI1
DI1 ACT
State of DI 1
ON/OFF
ON/OFF
R
r0722.1
BI2
DI2 ACT
State of DI 2
ON/OFF
ON/OFF
R
r0722.2
BI3
DI3 ACT
State of DI 3
ON/OFF
ON/OFF
R
r0722.3
BI4
DI4 ACT
State of DI 4
ON/OFF
ON/OFF
R
r0722.4
BI5
DI5 ACT
State of DI 5
ON/OFF
ON/OFF
R
r0722.5
BI7
DI7 ACT
State of AI 1 - used as DI ON/OFF
ON/OFF
R
r0722.11
BI8
DI8 ACT
State of AI 2 - used as DI
ON/OFF
ON/OFF
R
r0722.12
BI10
DO0 ACT
Controls DO 0 (relay 1)
ON/OFF
ON/OFF
R
read r747.0
BI11
DO1 ACT
Controls DO 1 (relay 2)
ON/OFF
ON/OFF
R
read r747.1
BI12
DO2 ACT
Status of DO2 (relay 3)
ON/OFF
ON/OFF
R
read r747.2
Table 6- 41 Binary output objects
Instance ID Object name
Description
Possible
values
Text active /
text inactive
Access type
Parameter
BO0
DO0 CMD
Controls DO 0 (relay 1)
ON/OFF
ON/OFF
C
p0730
BO1
DO1 CMD
Controls DO 1 (relay 2)
ON/OFF
ON/OFF
C
p0731
BO2
DO2 CMD
Controls DO 2 (relay 3)
ON/OFF
ON/OFF
C
p0732
Table 6- 42 Binary value objects
Instance
ID
Object
name
Description
Possible
values
Text active Text
inactive
Access
type
Parameter
BV0
RUN/
STOP ACT
Inverter status regardless of
command source
RUN/STOP
STOP
RUN
R
r0052.2
BV1
FWD/ REV Direction of rotation regardless of
command source
REV/ FWD
FWD
REV
R
r0052.14
BV2
FAULT
ACT
Fault status of inverter
FAULT/OK
FAULT
OK
R
r0052.3
BV3
WARN
ACT
Warning status of inverter
WARN/OK
WARN
OK
R
r0052.7
BV4
HAND/
AUTO ACT
Indicates the source of the
hand/auto inverter control
AUTO /
MANUAL
AUTO
LOCAL R
r0052.9
BV7
CTL
OVERRIDE
ACT
ACT indicates if the inverter
control has been transferred to
BACnet override control via BV93.
Note that the operator panel's
"Manual" operating mode has a
higher priority than the BACnet
override control.
ON/OFF
0
1
R
r2032[10]