Functions
7.4 Setpoint sources
Frequency inverters with Control Units CU230P-2 HVAC, CU230P-2 DP, CU230P-2 CAN
Operating Instructions, 01/2011, FW 4.4, A5E02430659B AD
201
Table 7- 22 Parameters for the "Jog" function
Parameter Description
p1055
Signal source for jogging 1 - jog bit 0 (factory setting: 0)
If you wish to jog via a digital input, then set p1055 = 722.x
p1056
Signal source for jogging 2 - jog bit 1 (factory setting: 0)
If you wish to jog via a digital input, then set p1056 = 722.x
p1058
Jogging 1 speed setpoint (factory setting, 150 rpm)
p1059
Jogging 2 speed setpoint (factory setting, 150 rpm)
7.4.5
Specifying the motor speed via the fieldbus
If you enter the setpoint via a fieldbus, you must connect the inverter to a higher-level
control. For additional information, see chapter Configuring the fieldbus (Page 97).
Interconnecting the fieldbus with the setpoint source
You have two options for using the fieldbus as the setpoint source:
1.
Using p0015, select a configuration that is suitable for your application.
Please refer to the section titled Selecting the interface assignments (Page 48) to find out
which configurations are available for your inverter.
2.
Interconnect main setpoint p1070 with the fieldbus.
Table 7- 23 Fieldbus as setpoint source
Parameter
Setpoint source
r2050[x]
Receive word no. x from RS485 interface
r2090[x]
Receive word no. x from PROFIBUS interface