Commissioning
4.2 Preparing for commissioning
Frequency inverters with Control Units CU230P-2 HVAC, CU230P-2 DP, CU230P-2 CAN
58
Operating Instructions, 01/2011, FW 4.4, A5E02430659B AD
4.2.1
Inverter factory setting
Factory settings of additional important parameters
Parameter Factory setting Meaning of the factory
setting
Name of the parameter and comments
p0010
0
Ready to be entered
Drive, commissioning parameter filter
p0100
0
Europe [50 Hz]
IEC/NEMA motor standard
•
IEC, Europe
•
NEMA, North America
Note: This parameter cannot cannot be changed in FW4.3.
p0300
1
Induction motor
Motor type selection (induction motors / synchronous motor)
p0304
400
[V]
Rated motor voltage (in accordance with the rating plate in V)
p0305
depends on the
Power Module
[A]
Rated motor current (in accordance with the rating plate in A)
p0307
depends on the
Power Module
[kW/hp]
Rated motor power (in accordance with the rating plate in
kW/hp)
p0308
0
[cos phi]
Rated motor power factor (in accordance with the rating plate in
cos 'phi'). If p0100 = 1, 2, then p0308 has no significance.
p0310
50
[Hz]
Rated motor frequency (in accordance with the rating plate in
Hz)
p0311
1395
[rpm]
Rated motor speed (in accordance with the rating plate in rpm)
p0335
0
Non-ventilated: Shaft-
mounted fan in the motor
Motor cooling type (specify the motor cooling system)
p0625
20
[°C]
Motor ambient temperature
p0640
200
[A]
Current limit (of the motor)
p0970
0
Locked
Reset drive parameters (restore to the factory settings)
P1080
0
[rpm]
Minimum speed
P1082
1500
[rpm]
Maximum speed
P1120
10
[s]
Ramp-function generator, ramp-up time
P1121
10
[s]
Ramp-function generator, ramp-down time
P1300
0
V/f control with linear
characteristic
Open-loop/closed-loop control operating mode