Technical data
10.2 Technical data, Power Modules
Frequency inverters with Control Units CU230P-2 HVAC, CU230P-2 DP, CU230P-2 CAN
Operating Instructions, 01/2011, FW 4.4, A5E02430659B AD
309
Table 10- 4 PM230 frame size A, 3-ph. 380 V AC… 480 V, ± 10 %
Order number Filter Class A
Filter Class B
6SL3223-0DE23-0AA0
6SL3223-0DE23-0BA0
Values based on Low Overload
● LO power
● LO input current
● LO output current
3 kW
8.0 A
7.7 A
Values based on High Overload
● HO power
● HO input current
● HO output current
2.2 kW
6.1 A
5.9 A
General values
● Power loss
● Fuse
● Cooling air requirement
● Cable cross-section for line and
motor connection
● Torque for line and motor and
motor connection
● Weight
0.12 kW
10 A
7 l/s
1.5 … 2.5 mm
2
0.5 Nm
4.3 kg
Table 10- 5 PM230 frame size B, 3-ph. 380 V AC… 480 V, ± 10 %
Order number Filter Class A
Filter Class B
6SL3223-0DE24-0AA0
6SL3223-0DE24-0BA0
6SL3223-0DE25-5AA0
6SL3223-0DE25-5BA0
6SL3223-0DE27-5AA0
6SL3223-0DE27-5BA0
Values based on Low Overload
● LO power
● LO input current
● LO output current
4 kW
10.5 A
10.2 A
5.5 kW
13.6 A
13.2 A
7.5 kW
18.6 A
18 A
Values based on High Overload
● HO power
● HO input current
● HO output current
3 kW
8.0 A
7.7 A
4 kW
10.5 A
10.2 A
5.5 kW
13.6 A
13.2 A
General values
● Power loss
● Fuse
● Cooling air requirement
● Cable cross-section for line and
motor connection
● Torque for line and motor and
motor connection
● Weight
0.14 kW
16 A
9 l/s
2.5 … 6 mm
2
0.5 Nm
6.3 kg
0.18 kW
20 A
9 l/s
4 … 6 mm
2
0.5 Nm
6.3 kg
0.24 kW
25 A
9 l/s
4 … 6 mm
2
0.5 Nm
6.3 kg
Содержание SINAMICS G120 CU230P-2
Страница 2: ......