Technical data
10.2 Technical data, Power Modules
Frequency inverters with Control Units CU230P-2 HVAC, CU230P-2 DP, CU230P-2 CAN
Operating Instructions, 01/2011, FW 4.4, A5E02430659B AD
311
Table 10- 8 PM230 frame size E, 3-ph. 380 V AC… 480 V, ± 10 %
Order number Filter Class A
Filter Class B
6SL3223-0DE33-7AA0
6SL3223-0DE33-7BA0
6SL3223-0DE34-5AA0
6SL3223-0DE34-5BA0
Values based on Low Overload
● LO power
● LO input current
● LO output current
37 kW
70 A
75 A
45 kW
84 A
90 A
Values based on High Overload
● HO power
● HO input current
● HO output current
30 kW
56 A
60 A
37 kW
70 A
75 A
General values
● Power loss
● Fuse
● Cooling air requirement
● Cable cross-section for line and
motor connection
● Torque for line and motor and
motor connection
● Weight
0.99 kW
100 A
39 l/s
25 … 50 mm
2
6 Nm
35.8 kg
1.2 kW
125 A
39 l/s
25 … 50 mm
2
6 Nm
35.8 kg
Table 10- 9 PM230 frame size F, 3-ph. 380 V AC… 480 V, ± 10 %
Order number Filter Class A
Filter Class B
6SL3223-0DE35-5AA0
6SL3223-0DE35-5BA0
6SL3223-0DE37-5AA0
6SL3223-0DE37-5BA0
6SL3223-0DE38-8AA0
6SL3223-0DE38-8BA0
Values based on Low Overload
● LO power
● LO input current
● LO output current
55 kW
102 A
110 A
75 kW
135 A
145 A
90 kW
166 A
178 A
Values based on High Overload
● HO power
● HO input current
● HO output current
45 kW
84 A
90 A
55 kW
102 A
110 A
75 kW
135 A
145 A
General values
● Power loss
● Fuse
● Cooling air requirement
● Cable cross-section for line and
motor connection
● Torque for line and motor and
motor connection
● Weight
1.4 kW
160 A
117 l/s
35 … 120 mm
2
13 Nm
70.0 kg
1.9 kW
200 A
117 l/s
35 … 120 mm
2
13 Nm
70.0 kg
2.3 kW
250 A
117 l/s
35 … 120 mm
2
13 Nm
70.0 kg
Содержание SINAMICS G120 CU230P-2
Страница 2: ......