SINAMICS DCM
List Manual (LH8), 02/2015, 6RX1800-0ED76
95
2 Parameters
2.2 List of parameters
Notice:
When changing over from one technological unit into another, or when changing the reference parameter, a
changeover is not made.
Description:
Sets the sensor type for the motor temperature monitoring.
Value:
0:
No sensor
2:
KTY84
Dependency:
Refer to: r0458
Description:
Runs the corresponding macro files.
The binector inputs of the corresponding command data set are appropriately interconnected.
The selected macro file must be available on the memory card/device memory.
Example:
p0700 = 6 --> macro file PM000006.ACX is run.
Dependency:
Refer to: p0015, p1000, p1500, r8571
Notice:
No errors were issued during quick commissioning (p3900 = 1) when writing to parameters of the QUICK_IBN group!
When executing a specific macro, the corresponding programmed settings are made and become active.
Note:
The macros in the specified directory are displayed in r8571. r8571 is not in the expert list of the commissioning
software.
Macros available as standard are described in the technical documentation of the particular product.
BI: Binector Input
CDS: Command Data Set
Description:
Runs the corresponding macro files.
The selected macro file must be available on the memory card/device memory.
Example:
p0700 = 6 --> macro file PM000006.ACX is run.
Dependency:
Refer to: r8571
Notice:
No errors were issued during quick commissioning (p3900 = 1) when writing to parameters of the QUICK_IBN group!
When executing a specific macro, the corresponding programmed settings are made and become active.
p0601[0...n]
Motor temperature sensor type / Mot_temp_sens type
DC_CTRL,
DC_CTRL_R,
DC_CTRL_R_S,
DC_CTRL_S
Can be changed:
C2(3), U, T
Calculated:
-
Access level:
2
Data type:
Integer16
Dyn. index:
MDS
Func. diagram:
-
P-Group:
Motor
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0 2
0
p0700[0...n]
Macro Binector Input (BI) / Macro BI
DC_CTRL,
DC_CTRL_R,
DC_CTRL_R_S,
DC_CTRL_S
Can be changed:
C2(1), T
Calculated:
-
Access level:
1
Data type:
Unsigned32
Dyn. index:
CDS, p0170
Func. diagram:
-
P-Group:
Commands
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0 999999
0
p0700
Macro Binector Input (BI) for TMs / Macro BI TM
TM15DI_DO, TM31
Can be changed:
C2(1), T
Calculated:
-
Access level:
1
Data type:
Unsigned32
Dyn. index:
-
Func. diagram:
-
P-Group:
Commands
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0 999999
0
Содержание SINAMICS DCM
Страница 1: ...s SINAMICS SINAMICS DCM List Manual 02 2015 Edition Answers for industry ...
Страница 2: ......
Страница 856: ...3 Function diagrams 3 23 Basic Operator Panel 20 BOP20 SINAMICS DCM 856 List Manual LH8 02 2015 6RX1800 0ED76 ...
Страница 1178: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS DCM 1178 List Manual LH8 02 2015 6RX1800 0ED76 ...
Страница 1192: ...A Appendix A 2 List of abbreviations SINAMICS DCM 1192 List Manual LH8 02 2015 6RX1800 0ED76 ...
Страница 1202: ...Index SINAMICS DCM 1202 List Manual LH8 02 2015 6RX1800 0ED76 ...
Страница 1203: ......