2 Parameters
2.2 List of parameters
SINAMICS DCM
258
List Manual (LH8), 02/2015, 6RX1800-0ED76
Description:
Displays the required memory in bytes for the actual parameterization.
This applies, if the trace for the measurement functions is used.
Index:
[0] = Trace 0
[1] = Trace 1
Dependency:
Refer to: r4799
Description:
Sets the trigger condition for the trace.
Value:
1:
Immediate trace start
2:
Positive edge
3:
Negative edge
4:
Entry to hysteresis band
5:
Leaving hysteresis band
6:
Trigger at bit mask
7:
Start with function generator
8:
Trigger at bit mask with edge
Index:
[0] = Trace 0
[1] = Trace 1
Description:
Selects the trigger signal for the trace.
Index:
[0] = Trace 0 parameter in BICO format
[1] = Trace 1 parameter in BICO format
[2] = Trace 0 PINx with DO Id and chart Id
[3] = Trace 0 PINx with block Id and PIN Id
[4] = Trace 1 PINy with DO Id and chart Id
[5] = Trace 1 PINy with block Id and PIN Id
Dependency:
Only effective when p4710 does not equal 1.
Note:
It only makes sense to trace the PINs using the commissioning software.
For index 2(4) and 3(5) equal to zero, index 0(1) can only be written and vice versa.
Re index 0 ... 1:
Here, the trigger signal for trace 0 or 1 is entered as parameter in the BICO format.
For trace with a physical address (p4789), the data type of the trigger signal is set here.
r4709[0...1]
Trace memory space required for measuring functions / Trace mem required
CU_DC, CU_DC_R,
CU_DC_R_S,
CU_DC_S
Can be changed:
-
Calculated:
-
Access level:
3
Data type:
Unsigned32
Dyn. index:
-
Func. diagram:
-
P-Group:
Trace and function generator
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
0
Min Max
Factory
setting
- -
-
p4710[0...1]
Trace trigger condition / Trace Trig_cond
CU_DC, CU_DC_R,
CU_DC_R_S,
CU_DC_S
Can be changed:
U, T
Calculated:
-
Access level:
3
Data type:
Integer16
Dyn. index:
-
Func. diagram:
-
P-Group:
Trace and function generator
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
0
Min Max
Factory
setting
1 8
2
p4711[0...5]
Trace trigger signal / Trace trig_signal
CU_DC, CU_DC_R,
CU_DC_R_S,
CU_DC_S
Can be changed:
U, T
Calculated:
-
Access level:
3
Data type:
Unsigned32
Dyn. index:
-
Func. diagram:
-
P-Group:
Trace and function generator
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
0
Min Max
Factory
setting
- -
0
Содержание SINAMICS DCM
Страница 1: ...s SINAMICS SINAMICS DCM List Manual 02 2015 Edition Answers for industry ...
Страница 2: ......
Страница 856: ...3 Function diagrams 3 23 Basic Operator Panel 20 BOP20 SINAMICS DCM 856 List Manual LH8 02 2015 6RX1800 0ED76 ...
Страница 1178: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS DCM 1178 List Manual LH8 02 2015 6RX1800 0ED76 ...
Страница 1192: ...A Appendix A 2 List of abbreviations SINAMICS DCM 1192 List Manual LH8 02 2015 6RX1800 0ED76 ...
Страница 1202: ...Index SINAMICS DCM 1202 List Manual LH8 02 2015 6RX1800 0ED76 ...
Страница 1203: ......