SINAMICS DCM
List Manual (LH8), 02/2015, 6RX1800-0ED76
1157
4 Faults and alarms
4.2 List of faults and alarms
F60056
Important parameter not set
Message value:
%1
Message class:
General drive fault (19)
Drive object:
DC_CTRL
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
Settings required for operation have not yet been made or connected components have not yet been commissioned.
Fault value (r0949, interpret decimal):
1: Actual value channel for speed controller not selected (p50083)
2: Rated armature current of the motor not set (p50100).
3: Rated field current of the motor not set (p50102).
Note:
Only necessary if p50082 > 0.
4: Rated DC current for the external field device not set (p51838).
Note:
Only necessary if p50082 >= 21.
5: Device commissioning not performed/completed (p0009 not equal to 0).
6: Drive commissioning not performed/completed (p0010 not equal to 0).
7: An internal field (p50082 = 1 to 4) has been selected for a device without a field power unit (option L10)
8: Field characteristic (p50120 ... p50139) not rising uniformly.
9: Reference speed (p2000) not set (factory setting value must be modified)!
10: Control Module: Connection of measurement cables for line voltage not set (p51821)
11: Control Module: Rated armature DC current not set (p51822).
Remedy:
Make the setting as appropriate for the fault value displayed.
F60057 (N, A)
Armature current sensing fault
Message value:
-
Message class:
Power electronics faulted (5)
Drive object:
DC_CTRL
Reaction:
OFF2 (NONE)
Acknowledge:
IMMEDIATELY
Cause:
The message is triggered if there are opposing current and torque directions.
Monitoring is active as soon as the current values overshoot the device rated current by 20%.
Note:
r50047[1]: Torque direction
r50047[2]: Current scan value
r50047[3]: Selected current sensing
r50047[3] = 1: Current transformer phase UV
r50047[3] = 2: Current transformer phase UW
r50047[3] = 3: Current transformer phase VW
r50047[3] = 4: External V-circuit
r50047[3] = 5: External current sensing (shunt)
r50047[3] = 6: Current sensing via analog input
See also: p51824 (Current transformer configuration), p51852 (Current actual value sensing analog input
configuration)
Remedy:
Check current transformer/shunt.
Reaction upon N:
NONE
Acknowl. upon N:
NONE
Reaction upon A:
NONE
Acknowl. upon A:
NONE
Содержание SINAMICS DCM
Страница 1: ...s SINAMICS SINAMICS DCM List Manual 02 2015 Edition Answers for industry ...
Страница 2: ......
Страница 856: ...3 Function diagrams 3 23 Basic Operator Panel 20 BOP20 SINAMICS DCM 856 List Manual LH8 02 2015 6RX1800 0ED76 ...
Страница 1178: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS DCM 1178 List Manual LH8 02 2015 6RX1800 0ED76 ...
Страница 1192: ...A Appendix A 2 List of abbreviations SINAMICS DCM 1192 List Manual LH8 02 2015 6RX1800 0ED76 ...
Страница 1202: ...Index SINAMICS DCM 1202 List Manual LH8 02 2015 6RX1800 0ED76 ...
Страница 1203: ......