SINAMICS DCM
List Manual (LH8), 02/2015, 6RX1800-0ED76
105
2 Parameters
2.2 List of parameters
Note:
Re bits 00, 01, 02, 04, 05, 06, 09:
For PROFIdrive, these signals are used for status word 1.
Description:
Sets the PROFIBUS address for PROFIBUS interface (X126) on the Control Unit.
The address can be set as follows:
Via p0918
--> The address is saved in a non-volatile fashion using the function "copy from RAM to ROM".
--> A change only becomes effective after a POWER ON.
Note:
Permissible PROFIBUS addresses: 1 ... 126
Address 126 is used for commissioning.
Every PROFIBUS address change only becomes effective after a POWER ON.
Description:
Sets the PROFIBUS address for PROFIBUS interface (X126) on the Control Unit.
The address can be set as follows:
Via p0918
--> The address is saved in a non-volatile fashion using the function "copy from RAM to ROM".
--> A change only becomes effective after a POWER ON.
Note:
Permissible PROFIBUS addresses: 1 ... 126
Address 126 is used for commissioning.
Every PROFIBUS address change only becomes effective after a POWER ON.
Description:
Sets the send and receive telegram.
Value:
390:
SIEMENS telegram 390, PZD-2/2
999:
Free telegram configuration with BICO
08
Controller enable
Yes
No
-
09
Control request
Yes
No
-
11
Pulses enabled
Yes
No
-
12
Open holding brake
Yes
No
-
13
Command close holding brake
Yes
No
-
14
Pulse enable from the brake control
Yes
No
-
15
Setpoint enable from the brake control
Yes
No
-
p0918
PROFIBUS address / PB address
CU_DC_R,
CU_DC_R_S
Can be changed:
T
Calculated:
-
Access level:
2
Data type:
Unsigned16
Dyn. index:
-
Func. diagram:
1520, 2410
P-Group:
Communications
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
1 126
125
p0918
PROFIBUS address / PB address
CU_DC, CU_DC_S
Can be changed:
T
Calculated:
-
Access level:
2
Data type:
Unsigned16
Dyn. index:
-
Func. diagram:
1520, 2410
P-Group:
Communications
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
1 126
126
p0922
IF1 PROFIdrive PZD telegram selection / IF1 PZD telegr
CU_DC, CU_DC_R,
CU_DC_R_S,
CU_DC_S
Can be changed:
C2(1), T
Calculated:
-
Access level:
1
Data type:
Unsigned16
Dyn. index:
-
Func. diagram:
1520, 2420
P-Group:
Communications
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
390 999
999
Содержание SINAMICS DCM
Страница 1: ...s SINAMICS SINAMICS DCM List Manual 02 2015 Edition Answers for industry ...
Страница 2: ......
Страница 856: ...3 Function diagrams 3 23 Basic Operator Panel 20 BOP20 SINAMICS DCM 856 List Manual LH8 02 2015 6RX1800 0ED76 ...
Страница 1178: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS DCM 1178 List Manual LH8 02 2015 6RX1800 0ED76 ...
Страница 1192: ...A Appendix A 2 List of abbreviations SINAMICS DCM 1192 List Manual LH8 02 2015 6RX1800 0ED76 ...
Страница 1202: ...Index SINAMICS DCM 1202 List Manual LH8 02 2015 6RX1800 0ED76 ...
Страница 1203: ......