SINAMICS DCM
List Manual (LH8), 02/2015, 6RX1800-0ED76
447
2 Parameters
2.2 List of parameters
The message is triggered when the threshold is undershot.
Once the value rises above the threshold plus the hysteresis, the message is withdrawn.
Dependency:
Refer to: p50370, p50593, r53025
Note:
The "Speed less than minimum speed reached" message is available as follows:
- r53025.6 (not inverted)
- r53025.7 (inverted)
Description:
Sets the hysteresis for the "Speed positive" message.
This parameter acts on the "Speed setpoint positive" message as well as on the "Speed actual value positive"
message.
Dependency:
Refer to: p50594, p50598, r53025
Note:
The "Speed positive" message is available as follows:
Setpoint:
- r53025.8 (not inverted)
- r53025.9 (inverted)
Actual value:
- r53025.12 (not inverted)
- r53025.13 (inverted)
Description:
Sets the threshold for the "Reference speed reached" message.
Dependency:
Refer to: p50374, p50375, p50592, r53025
Note:
The "Reference speed reached" message is available as follows:
- r53025.4 (not inverted)
- r53025.5 (inverted)
Description:
Sets the hysteresis for the "Reference speed reached" message.
The message is triggered when the threshold is overshot.
Once the value falls below the threshold minus the hysteresis, the message is withdrawn.
Dependency:
Refer to: p50373, p50375, p50592, r53025
p50372[0...n]
Messages speed positive hysteresis / Msg n > 0 hyst
DC_CTRL
Can be changed:
U, T
Calculated:
-
Access level:
2
Data type:
FloatingPoint32
Dyn. index:
DDS, p0180
Func. diagram:
8025
P-Group:
-
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
PERCENT
Expert list:
1
Min Max
Factory
setting
0.00 [%]
10.00 [%]
0.10 [%]
p50373[0...n]
Messages for reference speed threshold / Ref_speed thresh
DC_CTRL
Can be changed:
U, T
Calculated:
-
Access level:
2
Data type:
FloatingPoint32
Dyn. index:
DDS, p0180
Func. diagram:
8020
P-Group:
-
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
PERCENT
Expert list:
1
Min Max
Factory
setting
0.00 [%]
200.00 [%]
100.00 [%]
p50374[0...n]
Messages for reference speed hysteresis / Ref_speed hyst
DC_CTRL
Can be changed:
U, T
Calculated:
-
Access level:
2
Data type:
FloatingPoint32
Dyn. index:
DDS, p0180
Func. diagram:
8020
P-Group:
-
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
PERCENT
Expert list:
1
Min Max
Factory
setting
0.00 [%]
200.00 [%]
3.00 [%]
Содержание SINAMICS DCM
Страница 1: ...s SINAMICS SINAMICS DCM List Manual 02 2015 Edition Answers for industry ...
Страница 2: ......
Страница 856: ...3 Function diagrams 3 23 Basic Operator Panel 20 BOP20 SINAMICS DCM 856 List Manual LH8 02 2015 6RX1800 0ED76 ...
Страница 1178: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS DCM 1178 List Manual LH8 02 2015 6RX1800 0ED76 ...
Страница 1192: ...A Appendix A 2 List of abbreviations SINAMICS DCM 1192 List Manual LH8 02 2015 6RX1800 0ED76 ...
Страница 1202: ...Index SINAMICS DCM 1202 List Manual LH8 02 2015 6RX1800 0ED76 ...
Страница 1203: ......