SINAMICS DCM
List Manual (LH8), 02/2015, 6RX1800-0ED76
1167
4 Faults and alarms
4.2 List of faults and alarms
Reaction upon A:
NONE
Acknowl. upon A:
NONE
F60095 (N, A)
Power supply P24 overloaded
Message value:
-
Message class:
General drive fault (19)
Drive object:
DC_CTRL
Reaction:
OFF2 (NONE)
Acknowledge:
IMMEDIATELY
Cause:
Power supply P24 (+24 V) at terminal X177.9 or X177.10 is overloaded.
Note:
r50047[1]: Reference v10 V (in volts)
r50047[2]: Reference voltage -10 V (in volts)
r50047[3]: Module temperature (in °C)
Remedy:
Identify the reason for the overload (e.g. digital outputs) and rectify the situation.
Reaction upon N:
NONE
Acknowl. upon N:
NONE
Reaction upon A:
NONE
Acknowl. upon A:
NONE
F60096 (N, A)
Temperature sensor faulty
Message value:
%1
Message class:
Internal (DRIVE-CLiQ) communication error (12)
Drive object:
DC_CTRL
Reaction:
OFF2 (NONE, OFF1, OFF3)
Acknowledge:
IMMEDIATELY
Cause:
A cable break or a short circuit has been detected on at least one temperature sensor.
Fault value (r0949, interpret decimal):
1: A cable break has occurred.
2: A short circuit has occurred.
Note:
r50047[1] = 1: Temperature sensor 1
r50047[1] = 2: Temperature sensor 2
r50047[1] = 3: Temperature sensor 3
r50047[1] = 4: Temperature sensor gating module
r50047[1] = 5: Temperature sensor CUD module
r50047[1] = 6: Motor temperature sensor
r50047[2]: Value of the analog-to-digital converter
Remedy:
Evaluate the fault and, if the temperature sensor is faulty, run a wiring and performance check.
Reaction upon N:
NONE
Acknowl. upon N:
NONE
Reaction upon A:
NONE
Acknowl. upon A:
NONE
F60097 (N, A)
Power supply faulty
Message value:
-
Message class:
Power electronics faulted (5)
Drive object:
DC_CTRL
Reaction:
OFF2 (NONE)
Acknowledge:
IMMEDIATELY
Cause:
The power supply is not working correctly.
Note 1:
r50047[1]: Reference v10 V (in volts)
r50047[2]: Reference voltage -10 V (in volts)
r50047[3]: Module temperature (in °C)
Содержание SINAMICS DCM
Страница 1: ...s SINAMICS SINAMICS DCM List Manual 02 2015 Edition Answers for industry ...
Страница 2: ......
Страница 856: ...3 Function diagrams 3 23 Basic Operator Panel 20 BOP20 SINAMICS DCM 856 List Manual LH8 02 2015 6RX1800 0ED76 ...
Страница 1178: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS DCM 1178 List Manual LH8 02 2015 6RX1800 0ED76 ...
Страница 1192: ...A Appendix A 2 List of abbreviations SINAMICS DCM 1192 List Manual LH8 02 2015 6RX1800 0ED76 ...
Страница 1202: ...Index SINAMICS DCM 1202 List Manual LH8 02 2015 6RX1800 0ED76 ...