2 Parameters
2.2 List of parameters
SINAMICS DCM
290
List Manual (LH8), 02/2015, 6RX1800-0ED76
Description:
Displays the actual serial number of the Control Unit.
The individual characters of the serial number are displayed in the ASCII code in the indices.
For the commissioning software, the ASCII characters are displayed uncoded.
Dependency:
Refer to: p7765, p7766, p7767, p7768
Notice:
An ASCII table (excerpt) can be found, for example, in the appendix to the List Manual.
Note:
KHP: Know-How Protection
Description:
Sets the reference serial number for the Control Unit.
Using this parameter, if a Control Unit and/or a memory card is replaced at the end customer, the OEM can again
adapt the project to the modified hardware.
Dependency:
Refer to: p7765, p7766, p7767, p7768
Note:
KHP: Know-How Protection
- The OEM may only change this parameter for the use case "Sending encrypted SINAMICS data".
- SINAMICS only evaluates this parameter when powering up from the encrypted "Load into file system..." output or
when powering up from the encrypted PS files. The evaluation is only made when know-how protection and memory
card copy protection have been activated.
Description:
Displays the status for the write protection and know-how protection.
Dependency:
Refer to: p7761, p7765, p7766, p7767, p7768
Note:
KHP: Know-How Protection
Re bit 00:
Write protection can be activated/deactivated via p7761 on the Control Unit.
Re bit 01:
The know-how protection can be activated by entering a password (p7766 ... p7768).
r7758[0...19]
KHP Control Unit serial number / KHP CU ser_no
CU_DC, CU_DC_R,
CU_DC_R_S,
CU_DC_S
Can be changed:
-
Calculated:
-
Access level:
3
Data type:
Unsigned8
Dyn. index:
-
Func. diagram:
-
P-Group:
-
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
- -
-
p7759[0...19]
KHP Control Unit reference serial number / KHP CU ref ser_no
CU_DC, CU_DC_R,
CU_DC_R_S,
CU_DC_S
Can be changed:
T
Calculated:
-
Access level:
3
Data type:
Unsigned8
Dyn. index:
-
Func. diagram:
-
P-Group:
-
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
- -
-
r7760
Write protection/know-how protection status / Wr_prot/KHP stat
All objects
Can be changed:
-
Calculated:
-
Access level:
3
Data type:
Unsigned16
Dyn. index:
-
Func. diagram:
-
P-Group:
-
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
- -
-
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Write protection active
Yes
No
-
01
Know-how protection active
Yes
No
-
02
Know-how protection temporarily withdrawn Yes
No
-
03
Know-how protection cannot be deactivated Yes
No
-
04
Extended copy protection is active
Yes
No
-
05
Basic copy protection is active
Yes
No
-
06
Trace and measuring functions for
diagnostic purposes active
Yes
No
-
Содержание SINAMICS DCM
Страница 1: ...s SINAMICS SINAMICS DCM List Manual 02 2015 Edition Answers for industry ...
Страница 2: ......
Страница 856: ...3 Function diagrams 3 23 Basic Operator Panel 20 BOP20 SINAMICS DCM 856 List Manual LH8 02 2015 6RX1800 0ED76 ...
Страница 1178: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS DCM 1178 List Manual LH8 02 2015 6RX1800 0ED76 ...
Страница 1192: ...A Appendix A 2 List of abbreviations SINAMICS DCM 1192 List Manual LH8 02 2015 6RX1800 0ED76 ...
Страница 1202: ...Index SINAMICS DCM 1202 List Manual LH8 02 2015 6RX1800 0ED76 ...
Страница 1203: ......