SINAMICS DCM
List Manual (LH8), 02/2015, 6RX1800-0ED76
895
4 Faults and alarms
4.2 List of faults and alarms
F01305
Topology: Component number missing
Message value:
%1
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Drive object:
All objects
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
The component number from the topology was not parameterized (p0121 (for power unit, refer to p0107), p0131 (for
servo/vector drives, refer to p0107), p0141, p0151, p0161).
Fault value (r0949, interpret decimal):
Data set number.
Note:
The fault also occurs if encoders have been configured (p0187 to p0189) but no component numbers exist for them.
In this case, the fault value includes the drive data set number plus 100 * encoder number (e.g. 3xx, if a component
number was not entered in p0141 for encoder 3 (p0189)).
See also: p0121 (Power unit component number), p0141 (Encoder interface (Sensor Module) component number),
p0142 (Encoder component number), p0151 (Terminal Module component number), p0187 (Encoder 1 encoder data
set number), p0188 (Encoder 2 encoder data set number)
Remedy:
- enter missing component number.
- if required, remove the component and restart commissioning.
See also: p0121 (Power unit component number), p0141 (Encoder interface (Sensor Module) component number),
p0142 (Encoder component number), p0151 (Terminal Module component number), p0187 (Encoder 1 encoder data
set number), p0188 (Encoder 2 encoder data set number)
A01306
Firmware of the DRIVE-CLiQ component being updated
Message value:
%1
Message class:
General drive fault (19)
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
Firmware update is active for at least one DRIVE-CLiQ component.
Alarm value (r2124, interpret decimal):
Component number of the DRIVE-CLiQ component.
Remedy:
Not necessary.
This alarm automatically disappears after the firmware has been updated.
A01314
Topology: Component must not be present
Message value:
%1, to %2: %3, connection: %4
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
For a component, "de-activate and not present" is set but this component is still in the topology.
Alarm value (r2124, interpret hexadecimal):
ddccbbaa hex:
aa = component number
bb = component class of the component
cc = connection number
Note:
Component class and connection number are described in F01375.
Remedy:
- remove the corresponding component.
- change the setting "de-activate and not present".
Note:
Under "Topology --> Topology view" the commissioning software where relevant offers improved diagnostics
capability (e.g. setpoint/actual value comparison).
See also: p0105 (Activate/de-activate drive object), p0125 (Activate/de-activate power unit components), p0145
(Activate/de-activate encoder interface)
Содержание SINAMICS DCM
Страница 1: ...s SINAMICS SINAMICS DCM List Manual 02 2015 Edition Answers for industry ...
Страница 2: ......
Страница 856: ...3 Function diagrams 3 23 Basic Operator Panel 20 BOP20 SINAMICS DCM 856 List Manual LH8 02 2015 6RX1800 0ED76 ...
Страница 1178: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS DCM 1178 List Manual LH8 02 2015 6RX1800 0ED76 ...
Страница 1192: ...A Appendix A 2 List of abbreviations SINAMICS DCM 1192 List Manual LH8 02 2015 6RX1800 0ED76 ...
Страница 1202: ...Index SINAMICS DCM 1202 List Manual LH8 02 2015 6RX1800 0ED76 ...
Страница 1203: ......