4 Faults and alarms
4.2 List of faults and alarms
SINAMICS DCM
874
List Manual (LH8), 02/2015, 6RX1800-0ED76
A01016 (F)
Firmware changed
Message value:
%1
Message class:
Hardware / software error (1)
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
At least one firmware file in the directory was illegally changed on the non-volatile memory (memory card/device
memory) with respect to the version when shipped from the factory.
Alarm value (r2124, interpret decimal):
0: Checksum of one file is incorrect.
1: File missing.
2: Too many files.
3: Incorrect firmware version.
4: Incorrect checksum of the back-up file.
Remedy:
For the non-volatile memory for the firmware (memory card/device memory), restore the delivery condition.
Note:
The file involved can be read out using parameter r9925.
The status of the firmware check is displayed using r9926.
See also: r9925 (Firmware file incorrect), r9926 (Firmware check status)
Reaction upon F:
OFF2
Acknowl. upon F:
POWER ON
A01017
Component lists changed
Message value:
%1
Message class:
Hardware / software error (1)
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
On the memory card, one file in the directory /SIEMENS/SINAMICS/DATA or /ADDON/SINAMICS/DATA has been
illegally changed with respect to that supplied from the factory. No changes are permitted in this directory.
Alarm value (r2124, interpret decimal):
zyx dec: x = Problem, y = Directory, z = File name
x = 1: File does not exist.
x = 2: Firmware version of the file does not match the software version.
x = 3: File checksum is incorrect.
y = 0: Directory /SIEMENS/SINAMICS/DATA/
y = 1: Directory /ADDON/SINAMICS/DATA/
z = 0: File MOTARM.ACX
z = 1: File MOTSRM.ACX
z = 2: File MOTSLM.ACX
z = 3: File ENCDATA.ACX
z = 4: File FILTDATA.ACX
z = 5: File BRKDATA.ACX
z = 6: File DAT_BEAR.ACX
z = 7: File CFG_BEAR.ACX
z = 8: File ENC_GEAR.ACX
Remedy:
For the file on the memory card involved, restore the status originally supplied from the factory.
F01018
Booting has been interrupted several times
Message value:
-
Message class:
Hardware / software error (1)
Drive object:
All objects
Reaction:
NONE
Acknowledge:
POWER ON
Cause:
Module booting was interrupted several times. As a consequence, the module boots with the factory setting.
Содержание SINAMICS DCM
Страница 1: ...s SINAMICS SINAMICS DCM List Manual 02 2015 Edition Answers for industry ...
Страница 2: ......
Страница 856: ...3 Function diagrams 3 23 Basic Operator Panel 20 BOP20 SINAMICS DCM 856 List Manual LH8 02 2015 6RX1800 0ED76 ...
Страница 1178: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS DCM 1178 List Manual LH8 02 2015 6RX1800 0ED76 ...
Страница 1192: ...A Appendix A 2 List of abbreviations SINAMICS DCM 1192 List Manual LH8 02 2015 6RX1800 0ED76 ...
Страница 1202: ...Index SINAMICS DCM 1202 List Manual LH8 02 2015 6RX1800 0ED76 ...
Страница 1203: ......