2 Parameters
2.2 List of parameters
SINAMICS DCM
458
List Manual (LH8), 02/2015, 6RX1800-0ED76
Description:
Sets the signal source for the selection of the connectors (p50431[0 to 7]).
Dependency:
Refer to: p50431, p50432, p50680, p50681, r52204, r52209, r52210, r53170
Description:
Sets the signal sources for generating the fixed setpoint (CO: r52204).
Dependency:
Refer to: p50430, p50432, p50680, p50681, r52204, r52209, r52210, r53170
Description:
Setting to enable or disable the impact of the individual fixed setpoints when generating signal r53170.10, "Bypass
ramp-function generator".
Value:
0:
Inhibit
1:
Enable
Dependency:
Refer to: r53170
Note:
[0] = Enable bypassing of ramp-function generator at fixed setpoint 0
...
[7] = Enable bypassing of ramp-function generator at fixed setpoint 7
Description:
Sets the signal source for the default setpoint.
p50430[0...7]
BI: Fixed setpoint signal source for connector selection / Fix set conn sig s
DC_CTRL
Can be changed:
T
Calculated:
-
Access level:
2
Data type:
Unsigned32 / Binary
Dyn. index:
-
Func. diagram:
3115
P-Group:
-
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
- -
0
p50431[0...7]
CI: Signal source for fixed setpoint / Fix set sig s
DC_CTRL
Can be changed:
T
Calculated:
-
Access level:
2
Data type:
Unsigned32 / FloatingPoint32
Dyn. index:
-
Func. diagram:
3115
P-Group:
-
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
PERCENT
Expert list:
1
Min Max
Factory
setting
- -
0
p50432[0...7]
Fixed setpoint bypass ramp-function generator / Fix set bypass RFG
DC_CTRL
Can be changed:
T
Calculated:
-
Access level:
2
Data type:
Integer16
Dyn. index:
-
Func. diagram:
3115
P-Group:
-
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0 1
0
p50433[0...n]
CI: Signal source for default setpoint / Def set sig s
DC_CTRL
Can be changed:
T
Calculated:
-
Access level:
2
Data type:
Unsigned32 / FloatingPoint32
Dyn. index:
CDS, p0170
Func. diagram:
3113
P-Group:
-
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
PERCENT
Expert list:
1
Min Max
Factory
setting
- -
52011[0]
Содержание SINAMICS DCM
Страница 1: ...s SINAMICS SINAMICS DCM List Manual 02 2015 Edition Answers for industry ...
Страница 2: ......
Страница 856: ...3 Function diagrams 3 23 Basic Operator Panel 20 BOP20 SINAMICS DCM 856 List Manual LH8 02 2015 6RX1800 0ED76 ...
Страница 1178: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS DCM 1178 List Manual LH8 02 2015 6RX1800 0ED76 ...
Страница 1192: ...A Appendix A 2 List of abbreviations SINAMICS DCM 1192 List Manual LH8 02 2015 6RX1800 0ED76 ...
Страница 1202: ...Index SINAMICS DCM 1202 List Manual LH8 02 2015 6RX1800 0ED76 ...
Страница 1203: ......