SINAMICS DCM
List Manual (LH8), 02/2015, 6RX1800-0ED76
127
2 Parameters
2.2 List of parameters
Description:
Sets the number of 16-bit words in the PZD part of the USS telegram for the field bus interface.
Dependency:
Refer to: p2030
Note:
The parameter is not influenced by setting the factory setting.
Description:
Sets the number of 16-bit words in the PKW part of the USS telegram for the field bus interface.
Value:
0:
PKW 0 words
3:
PKW 3 words
4:
PKW 4 words
127:
PKW variable
Dependency:
Refer to: p2030
Note:
The parameter is not influenced by setting the factory setting.
Description:
Displays the receive errors on the field bus interface (USS).
Index:
[0] = Number of error-free telegrams
[1] = Number of rejected telegrams
[2] = Number of framing errors
[3] = Number of overrun errors
[4] = Number of parity errors
[5] = Number of starting character errors
[6] = Number of checksum errors
[7] = Number of length errors
Description:
Sets the communication protocol for the field bus interface.
Value:
0:
No protocol
1:
USS
3:
PROFIBUS
p2022
Field bus int USS PZD no. / Field bus USS PZD
CU_DC, CU_DC_R,
CU_DC_R_S,
CU_DC_S
Can be changed:
T
Calculated:
-
Access level:
2
Data type:
Unsigned16
Dyn. index:
-
Func. diagram:
9310
P-Group:
Communications
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0 16
2
p2023
Field bus int USS PKW no. / Field bus USS PKW
CU_DC, CU_DC_R,
CU_DC_R_S,
CU_DC_S
Can be changed:
T
Calculated:
-
Access level:
2
Data type:
Integer16
Dyn. index:
-
Func. diagram:
9310
P-Group:
Communications
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0 127
127
r2029[0...7]
Field bus int error statistics / Field bus error
CU_DC, CU_DC_R,
CU_DC_R_S,
CU_DC_S
Can be changed:
-
Calculated:
-
Access level:
3
Data type:
Unsigned32
Dyn. index:
-
Func. diagram:
9310
P-Group:
Communications
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
- -
-
p2030
Field bus int protocol selection / Field bus protocol
CU_DC, CU_DC_R,
CU_DC_R_S,
CU_DC_S
Can be changed:
T
Calculated:
-
Access level:
1
Data type:
Integer16
Dyn. index:
-
Func. diagram:
-
P-Group:
Communications
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0 3
3
Содержание SINAMICS DCM
Страница 1: ...s SINAMICS SINAMICS DCM List Manual 02 2015 Edition Answers for industry ...
Страница 2: ......
Страница 856: ...3 Function diagrams 3 23 Basic Operator Panel 20 BOP20 SINAMICS DCM 856 List Manual LH8 02 2015 6RX1800 0ED76 ...
Страница 1178: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS DCM 1178 List Manual LH8 02 2015 6RX1800 0ED76 ...
Страница 1192: ...A Appendix A 2 List of abbreviations SINAMICS DCM 1192 List Manual LH8 02 2015 6RX1800 0ED76 ...
Страница 1202: ...Index SINAMICS DCM 1202 List Manual LH8 02 2015 6RX1800 0ED76 ...
Страница 1203: ......