SINAMICS DCM
List Manual (LH8), 02/2015, 6RX1800-0ED76
1161
4 Faults and alarms
4.2 List of faults and alarms
47: Analog input XT1.103/104, voltage input, -270 V incorrect value
48: Analog input XT1.103/104, voltage input, reference value incorrect
49: Analog output 0 (X177.49/50), offset incorrect value
50: Analog output 0 (X177.49/50), -10 V incorrect value
51: Analog output 0 (X177.49/50), +10 V incorrect value
52: Analog output 0 (X177.49/50), reference value incorrect
53: Analog output 1 (X177.51/52), offset incorrect value
54: Analog output 1 (X177.51/52), -10 V incorrect value
55: Analog output 1 (X177.51/52), +10 V incorrect value
56: Analog output 1 (X177.51/52), reference value incorrect
Note:
r50047[1]: Incorrect calibration value
Remedy:
Replace the electronics module with the incorrect calibration values.
Reaction upon N:
NONE
Acknowl. upon N:
NONE
Reaction upon A:
NONE
Acknowl. upon A:
NONE
F60064 (N, A)
Error communicating with second processor TMS320
Message value:
-
Message class:
Internal (DRIVE-CLiQ) communication error (12)
Drive object:
DC_CTRL
Reaction:
OFF2 (NONE)
Acknowledge:
IMMEDIATELY
Cause:
Communication with the second processor (TMS320) has failed.
Note:
r50047[1]: Communication counter in send direction
r50047[2]: Communication counter in receive direction
Remedy:
Carry out a POWER ON (power off/on) for all components.
Reaction upon N:
NONE
Acknowl. upon N:
NONE
Reaction upon A:
NONE
Acknowl. upon A:
NONE
F60065 (N, A)
Software update on second processor (TMS320) failed
Message value:
%1
Message class:
Hardware/software error (1)
Drive object:
DC_CTRL
Reaction:
OFF2 (NONE)
Acknowledge:
IMMEDIATELY
Cause:
The updating of the software for the second processor (TMS320) has failed.
Fault value (r0949, interpret decimal):
This value indicates the state in which the fault occurred.
2: Wait for the TMS320 bootloader to be ready.
3: Check the version of the TMS320 bootloader.
4: Check the version of the TMS320 application software.
5: Wait for the TMS320 to exit the bootloader.
6: Wait for theTMS320 to load its Flash API.
7: Wait for theTMS320 to delete its Flash EPROM.
8: Send a section of code 8 KB in size to the TMS320.
9: Wait for the TMS320 to request a new 8 KB section of code.
10: Wait until the TMS320 application software has been started.
11: Wait until the TMS320 is ready for a new command.
Содержание SINAMICS DCM
Страница 1: ...s SINAMICS SINAMICS DCM List Manual 02 2015 Edition Answers for industry ...
Страница 2: ......
Страница 856: ...3 Function diagrams 3 23 Basic Operator Panel 20 BOP20 SINAMICS DCM 856 List Manual LH8 02 2015 6RX1800 0ED76 ...
Страница 1178: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS DCM 1178 List Manual LH8 02 2015 6RX1800 0ED76 ...
Страница 1192: ...A Appendix A 2 List of abbreviations SINAMICS DCM 1192 List Manual LH8 02 2015 6RX1800 0ED76 ...
Страница 1202: ...Index SINAMICS DCM 1202 List Manual LH8 02 2015 6RX1800 0ED76 ...
Страница 1203: ......