SINAMICS DCM
List Manual (LH8), 02/2015, 6RX1800-0ED76
429
2 Parameters
2.2 List of parameters
Description:
Sets activation/de-activation of the integral component on the field current controller.
Value:
0:
Deactivated
1:
Activated
Dependency:
Refer to: p50255, p50256
Note:
If value = 0:
The integral component of the field current controller is kept constantly at zero (i.e. the field current controller
functions solely as a proportional controller).
Description:
Sets the P gain of the field current controller.
Dependency:
Refer to: p50256
Note:
The parameter is set automatically during the optimization run for closed-loop field current control (p50051 = 24).
Description:
Sets the integral time of the field current controller.
Dependency:
Refer to: p50255
Note:
The parameter is set automatically during the optimization run for closed-loop field current control (p50051 = 24).
Description:
Sets the standstill field for closed-loop field current control.
Dependency:
Refer to: p50692
Note:
The field current is reduced to this value when the "Automatic field current reduction" function is parameterized
(p50082 = 2) or in the case of signal-driven selection of the ""Standstill excitation" function (p50692).
p50254[0...n]
Field current controller integral component activation / I_field_ctr I comp
DC_CTRL
Can be changed:
T
Calculated:
-
Access level:
2
Data type:
Integer16
Dyn. index:
DDS, p0180
Func. diagram:
6910
P-Group:
-
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0 1
1
p50255[0...n]
Field current controller P gain / I_field ctr Kp
DC_CTRL
Can be changed:
U, T
Calculated:
-
Access level:
2
Data type:
FloatingPoint32
Dyn. index:
DDS, p0180
Func. diagram:
6908
P-Group:
-
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0.01 100.00
5.00
p50256[0...n]
Field current controller integral time / I_field ctr Tn
DC_CTRL
Can be changed:
U, T
Calculated:
-
Access level:
2
Data type:
FloatingPoint32
Dyn. index:
DDS, p0180
Func. diagram:
6908
P-Group:
-
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0.001 [s]
10.000 [s]
0.200 [s]
p50257[0...n]
Closed-loop field current control standstill field / If_ctr stst_field
DC_CTRL
Can be changed:
U, T
Calculated:
-
Access level:
2
Data type:
FloatingPoint32
Dyn. index:
DDS, p0180
Func. diagram:
6910
P-Group:
-
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
PERCENT
Expert list:
1
Min Max
Factory
setting
0.0 [%]
100.0 [%]
0.0 [%]
Содержание SINAMICS DCM
Страница 1: ...s SINAMICS SINAMICS DCM List Manual 02 2015 Edition Answers for industry ...
Страница 2: ......
Страница 856: ...3 Function diagrams 3 23 Basic Operator Panel 20 BOP20 SINAMICS DCM 856 List Manual LH8 02 2015 6RX1800 0ED76 ...
Страница 1178: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS DCM 1178 List Manual LH8 02 2015 6RX1800 0ED76 ...
Страница 1192: ...A Appendix A 2 List of abbreviations SINAMICS DCM 1192 List Manual LH8 02 2015 6RX1800 0ED76 ...
Страница 1202: ...Index SINAMICS DCM 1202 List Manual LH8 02 2015 6RX1800 0ED76 ...
Страница 1203: ......