4 Faults and alarms
4.1 Overview of faults and alarms
SINAMICS DCM
858
List Manual (LH8), 02/2015, 6RX1800-0ED76
4.1
Overview of faults and alarms
4.1.1
General information on faults and alarms
Fault/alarm displays
In the case of a fault, the drive signals the corresponding fault(s) and/or alarm(s).
The following methods are available for displaying faults and alarms:
•
Display via the fault and alarm buffer for PROFIBUS.
•
In online operation, display via the commissioning software.
Differences between faults and alarms
The differences between faults and alarms are as follows:
Table 4-1
Differences between faults and alarms
Type
Description
Faults
What happens when a fault occurs?
•
The appropriate fault reaction is initiated.
•
Status signal ZSW1.3 is set.
•
The fault is entered into the fault buffer.
How are faults removed?
•
Remove the original cause of the fault.
•
Acknowledge the fault.
Alarms
What happens when an alarm occurs?
•
Status signal ZSW1.7 is set.
•
The alarm is entered into the alarm buffer.
How are alarms removed?
•
Alarms acknowledge themselves. If the cause of the alarm is no longer
present, they automatically reset themselves.
Содержание SINAMICS DCM
Страница 1: ...s SINAMICS SINAMICS DCM List Manual 02 2015 Edition Answers for industry ...
Страница 2: ......
Страница 856: ...3 Function diagrams 3 23 Basic Operator Panel 20 BOP20 SINAMICS DCM 856 List Manual LH8 02 2015 6RX1800 0ED76 ...
Страница 1178: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS DCM 1178 List Manual LH8 02 2015 6RX1800 0ED76 ...
Страница 1192: ...A Appendix A 2 List of abbreviations SINAMICS DCM 1192 List Manual LH8 02 2015 6RX1800 0ED76 ...
Страница 1202: ...Index SINAMICS DCM 1202 List Manual LH8 02 2015 6RX1800 0ED76 ...
Страница 1203: ......