2 Parameters
2.2 List of parameters
SINAMICS DCM
202
List Manual (LH8), 02/2015, 6RX1800-0ED76
External fault 3 is initiated by the following AND logic operation:
- BI: p2108 negated
- BI: p3111
- BI: p3112 negated
Dependency:
Refer to: p2108, p3110, p3111
Description:
Display and BICO output for the status of the NAMUR message bit bar.
The faults and alarms are assigned to the appropriate signaling/message classes and influence a specific message
bit.
Note:
Re bit 00:
Hardware or software malfunction was identified. Carry out a POWER ON of the component involved. If it occurs
again, contact the hotline.
Re bit 01:
A line supply fault has occurred (phase failure, voltage level, ...). Check the line supply / fuses. Check the supply
voltage. Check the wiring.
Re bit 02:
The DC link voltage has assumed an inadmissibly high value. Check the dimensioning of the system (line supply,
reactor, voltages). Check the infeed settings.
Re bit 03:
An inadmissible operating state of the power electronics was identified (overcurrent, overtemperature, IGBT failure,
...). Check that the permissible load cycles are maintained. Check the ambient temperatures (fan).
Re bit 04:
The temperature in the component has exceeded the highest permissible limit. Check the ambient temperature /
control cabinet cooling.
Re bit 05:
A ground fault / inter-phase short-circuit was detected in the power cables or in the motor windings. Check the power
cable (connection). Check the motor.
Re bit 06:
The motor was operated outside the permissible limits (temperature, current, torque, ...). Check the load cycles and
limits that have been set. Check the ambient temperature / motor cooling.
Re bit 07:
The communication to the higher-level control system (internal coupling, PROFIBUS, PROFINET, ...) is faulted or
interrupted. Check the state of the higher-level control system. Check the communication connection/wiring. Check
the bus configuration / clock cycles.
Re bit 08:
A safety operation monitoring function (Safety) has detected an error.
r3113.0...15
CO/BO: NAMUR message bit bar / NAMUR bit bar
All objects
Can be changed:
-
Calculated:
-
Access level:
3
Data type:
Unsigned16
Dyn. index:
-
Func. diagram:
-
P-Group:
Messages
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
- -
-
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Fault converter information
electronics/software error
Yes
No
-
01
Network fault
Yes
No
-
02
DC link overvoltage
Yes
No
-
03
Fault drive converter power electronics
Yes
No
-
04
Drive converter overtemperature
Yes
No
-
05
Ground fault
Yes
No
-
06
Motor overload
Yes
No
-
07
Bus error
Yes
No
-
08
External safety-relevant shutdown
Yes
No
-
09
Mot encoder fault
Yes
No
-
10
Error communication internal
Yes
No
-
11
Fault infeed
Yes
No
-
15
Other faults
Yes
No
-
Содержание SINAMICS DCM
Страница 1: ...s SINAMICS SINAMICS DCM List Manual 02 2015 Edition Answers for industry ...
Страница 2: ......
Страница 856: ...3 Function diagrams 3 23 Basic Operator Panel 20 BOP20 SINAMICS DCM 856 List Manual LH8 02 2015 6RX1800 0ED76 ...
Страница 1178: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS DCM 1178 List Manual LH8 02 2015 6RX1800 0ED76 ...
Страница 1192: ...A Appendix A 2 List of abbreviations SINAMICS DCM 1192 List Manual LH8 02 2015 6RX1800 0ED76 ...
Страница 1202: ...Index SINAMICS DCM 1202 List Manual LH8 02 2015 6RX1800 0ED76 ...
Страница 1203: ......