2 Parameters
2.2 List of parameters
SINAMICS DCM
414
List Manual (LH8), 02/2015, 6RX1800-0ED76
Note:
If value = 0:
The proportional component of the armature current controller is kept constantly at zero (i.e. the armature current
controller functions solely as an integral controller).
Description:
Sets the signal source to enable a torque direction in the event of a change in torque direction.
1 signal:
Enable available for M0 or MI.
0 signal:
Enable available for M0 or MII.
Description:
Setting to activate/de-activate the calculation of the thyristor blocking voltage.
Value:
0:
De-activating
1:
Activating
Note:
The calculation of the thyristor blocking voltage can only be activated if the hardware (Power Interface Module)
supports this function.
This parameter is only evaluated once while powering up, i.e. a change only becomes effective after a new start or
after powering up with saved parameters (p0976 = 11).
Description:
Setting to select torque limiting or current limitation.
Value:
0:
Current lim
1:
Torque limiting
Dependency:
If p50169 = 1 or p50170 = 1:
A valid field characteristic (p50117 = 1) is required, otherwise fault F60055 will be output on power-up. If this setting
is selected, the optimization run for field weakening must be performed in advance (p50051 = 27).
Parameter p50263 defines the input variable for determining the motor flux.
If p50169 = 1 and p50170 = 1:
This is an invalid setting.
If p50170 = 1, it will not be possible to set p50169 = 1.
Refer to: p50051, p50117, p50263
p50165[0...n]
BI: Signal source for change in torque direction enable / Torq dir en sig s
DC_CTRL
Can be changed:
T
Calculated:
-
Access level:
2
Data type:
Unsigned32 / Binary
Dyn. index:
CDS, p0170
Func. diagram:
6860
P-Group:
-
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
- -
53190.0
p50166
Thyristor blocking voltage calculation activation / Thy_block_calc act
DC_CTRL
Can be changed:
T
Calculated:
-
Access level:
3
Data type:
Integer16
Dyn. index:
-
Func. diagram:
6860
P-Group:
-
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0 1
0
p50169[0...n]
Torque limiting selection torque limiting/current limitation / T lim sel T/I_lim
DC_CTRL
Can be changed:
T
Calculated:
-
Access level:
2
Data type:
Integer16
Dyn. index:
DDS, p0180
Func. diagram:
6830
P-Group:
-
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0 1
1
Содержание SINAMICS DCM
Страница 1: ...s SINAMICS SINAMICS DCM List Manual 02 2015 Edition Answers for industry ...
Страница 2: ......
Страница 856: ...3 Function diagrams 3 23 Basic Operator Panel 20 BOP20 SINAMICS DCM 856 List Manual LH8 02 2015 6RX1800 0ED76 ...
Страница 1178: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS DCM 1178 List Manual LH8 02 2015 6RX1800 0ED76 ...
Страница 1192: ...A Appendix A 2 List of abbreviations SINAMICS DCM 1192 List Manual LH8 02 2015 6RX1800 0ED76 ...
Страница 1202: ...Index SINAMICS DCM 1202 List Manual LH8 02 2015 6RX1800 0ED76 ...
Страница 1203: ......