SINAMICS DCM
List Manual (LH8), 02/2015, 6RX1800-0ED76
367
2 Parameters
2.2 List of parameters
Description:
Sets the configuration for the DRIVE-CLiQ detailed diagnostics (r9943).
Using the detailed diagnostics, it is possible to investigate data transfer errors on an individual connection, selected
using p9942.
Value:
0:
Inactive
1:
Sum send and receive errors
2:
Only send errors
3:
Only receive errors
4:
Siemens internal
5:
Siemens internal
6:
Siemens internal
Dependency:
The functions in p9938 can only be set for p9937.0 = 0.
Refer to: r9936, p9937, p9939, p9942
Notice:
If value = 0:
- detailed diagnostics is inactive.
- the error counter is active (r9936).
If value > 0:
- the error counter is inactive (r9936).
- the detailed diagnostics as configured is active (r9943).
Description:
Sets the time interval for recording the error counter in r9943.
Dependency:
Refer to: r9936, p9938, p9942, r9943
Description:
For p9941 =1, the serial numbers of all components in the target topology are deleted (zero is written).
Through activation and de-activation this enables the actual topology components to be newly assigned to the target
topology components.
Note:
p9941 is automatically set to 0 at the end of the operation.
A warm restart is triggered automatically after p0009 = 0.
p9938
DRIVE-CLiQ detailed diagnostics configuration / DQ diag config
CU_DC, CU_DC_R,
CU_DC_R_S,
CU_DC_S
Can be changed:
U, T
Calculated:
-
Access level:
4
Data type:
Integer16
Dyn. index:
-
Func. diagram:
-
P-Group:
-
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0 6
0
p9939
DRIVE-CLiQ detailed diagnostics time interval / DQ detail t_interv
CU_DC, CU_DC_R,
CU_DC_R_S,
CU_DC_S
Can be changed:
U, T
Calculated:
-
Access level:
4
Data type:
FloatingPoint32
Dyn. index:
-
Func. diagram:
-
P-Group:
-
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
1 [s]
3600 [s]
1 [s]
p9941
Target topology feature delete all components / Feature delete
CU_DC, CU_DC_R,
CU_DC_R_S,
CU_DC_S
Can be changed:
C1(1)
Calculated:
-
Access level:
3
Data type:
Unsigned32
Dyn. index:
-
Func. diagram:
-
P-Group:
Topology
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
0
Min Max
Factory
setting
0 1
0
Содержание SINAMICS DCM
Страница 1: ...s SINAMICS SINAMICS DCM List Manual 02 2015 Edition Answers for industry ...
Страница 2: ......
Страница 856: ...3 Function diagrams 3 23 Basic Operator Panel 20 BOP20 SINAMICS DCM 856 List Manual LH8 02 2015 6RX1800 0ED76 ...
Страница 1178: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS DCM 1178 List Manual LH8 02 2015 6RX1800 0ED76 ...
Страница 1192: ...A Appendix A 2 List of abbreviations SINAMICS DCM 1192 List Manual LH8 02 2015 6RX1800 0ED76 ...
Страница 1202: ...Index SINAMICS DCM 1202 List Manual LH8 02 2015 6RX1800 0ED76 ...
Страница 1203: ......