4 Faults and alarms
4.2 List of faults and alarms
SINAMICS DCM
964
List Manual (LH8), 02/2015, 6RX1800-0ED76
A08520 (F)
PN/COMM BOARD: Non-cyclic channel error
Message value:
%1
Message class:
Communication error to the higher-level control system (9)
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
The memory or the buffer status of the non-cyclic channel has an error.
Alarm value (r2124, interpret decimal):
0: Error in the buffer status.
1: Error in the memory.
Remedy:
Check communications link.
Reaction upon F:
NONE (OFF1, OFF2, OFF3)
Acknowl. upon F:
IMMEDIATELY
A08526 (F)
PN/COMM BOARD: No cyclic connection
Message value:
-
Message class:
Communication error to the higher-level control system (9)
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
There is no cyclic connection to the control.
Remedy:
Establish the cyclic connection and activate the control with cyclic operation.
For PROFINET, check the parameters "Name of Station" and "IP of Station" (r61000, r61001).
If a CBE20 is inserted and PROFIBUS is to communicate via PZD Interface 1, then this must be parameterized using
the STARTER commissioning tool or directly using p8839.
Reaction upon F:
NONE (OFF1)
Acknowl. upon F:
IMMEDIATELY
A08530 (F)
PN/COMM BOARD: Message channel error
Message value:
%1
Message class:
Communication error to the higher-level control system (9)
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
The memory or the buffer status of the message channel has an error.
Alarm value (r2124, interpret decimal):
0: Error in the buffer status.
1: Error in the memory.
Remedy:
Check communications link.
Reaction upon F:
NONE (OFF1, OFF2, OFF3)
Acknowl. upon F:
IMMEDIATELY
A08550
PZD Interface Hardware assignment error
Message value:
%1
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Drive object:
CU_DC, CU_DC_R, CU_DC_R_S, CU_DC_S
Reaction:
NONE
Acknowledge:
NONE
Cause:
The assignment of the hardware to the PZD interface has been incorrectly parameterized.
Alarm value (r2124, interpret decimal):
3: Assigned COMM BOARD missing.
See also: p8839 (PZD interface hardware assignment)
Remedy:
Check the parameterization and if required, correct (p8839).
Содержание SINAMICS DCM
Страница 1: ...s SINAMICS SINAMICS DCM List Manual 02 2015 Edition Answers for industry ...
Страница 2: ......
Страница 856: ...3 Function diagrams 3 23 Basic Operator Panel 20 BOP20 SINAMICS DCM 856 List Manual LH8 02 2015 6RX1800 0ED76 ...
Страница 1178: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS DCM 1178 List Manual LH8 02 2015 6RX1800 0ED76 ...
Страница 1192: ...A Appendix A 2 List of abbreviations SINAMICS DCM 1192 List Manual LH8 02 2015 6RX1800 0ED76 ...
Страница 1202: ...Index SINAMICS DCM 1202 List Manual LH8 02 2015 6RX1800 0ED76 ...
Страница 1203: ......