2 Parameters
2.2 List of parameters
SINAMICS DCM
498
List Manual (LH8), 02/2015, 6RX1800-0ED76
Description:
Sets the signal source for feedback from the line contactor.
The feedback signal is checked and fault F60104 is triggered in the following cases:
- If, following power-up, a 1 signal is not detected within the time set in p50095 (in other words, if the line contactor
has not closed).
- If a 0 signal is detected during operation.
Note:
Feedback from the line contactor can be achieved by integrating one of the line contactor's auxiliary contacts into the
device control.
Description:
Sets the signal source for the selection of standstill field injection.
Dependency:
Refer to: F60045
Description:
Sets the signal source to enable the EMF controller.
Description:
Sets the signal source to enable the torque limits to be changed over.
Dependency:
Refer to: p50180, p50181, p50182, p50183
Note:
1 signal: Changeover enabled
0 signal: Changeover disabled
p50691[0...n]
BI: Sequence control line contactor feedback / Line cont feedb
DC_CTRL
Can be changed:
T
Calculated:
-
Access level:
2
Data type:
Unsigned32 / Binary
Dyn. index:
CDS, p0170
Func. diagram:
2651
P-Group:
-
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
- -
1
p50692[0...n]
BI: Cl-loop field curr ctrl sig source for inject of standst field / If_ctr stst sig s
DC_CTRL
Can be changed:
T
Calculated:
-
Access level:
2
Data type:
Unsigned32 / Binary
Dyn. index:
CDS, p0170
Func. diagram:
6910, 8046
P-Group:
-
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
- -
0
p50693[0...n]
BI: EMF controller enable signal source / EMF ctr ena sig s
DC_CTRL
Can be changed:
T
Calculated:
-
Access level:
2
Data type:
Unsigned32 / Binary
Dyn. index:
CDS, p0170
Func. diagram:
6900
P-Group:
-
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
- -
1
p50694[0...n]
BI: Torque limiting signal source to enable changeover / T lim ch ena sig s
DC_CTRL
Can be changed:
T
Calculated:
-
Access level:
2
Data type:
Unsigned32 / Binary
Dyn. index:
CDS, p0170
Func. diagram:
6825
P-Group:
-
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
- -
0
Содержание SINAMICS DCM
Страница 1: ...s SINAMICS SINAMICS DCM List Manual 02 2015 Edition Answers for industry ...
Страница 2: ......
Страница 856: ...3 Function diagrams 3 23 Basic Operator Panel 20 BOP20 SINAMICS DCM 856 List Manual LH8 02 2015 6RX1800 0ED76 ...
Страница 1178: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS DCM 1178 List Manual LH8 02 2015 6RX1800 0ED76 ...
Страница 1192: ...A Appendix A 2 List of abbreviations SINAMICS DCM 1192 List Manual LH8 02 2015 6RX1800 0ED76 ...
Страница 1202: ...Index SINAMICS DCM 1202 List Manual LH8 02 2015 6RX1800 0ED76 ...
Страница 1203: ......