484
Temperature Input Unit Functions
Section 11-5
Note
1.
The bias compensation value may not be accepted if there is a large tem-
perature difference between the Terminal Block and ZERO-CON (0
°
C
bath). If this problem occurs, correct the adjustment system by using a
ZERO-CON compatible with the sensor being adjusted or other means.
2.
Always test the indication accuracy after making user adjustments to verify
that the adjustments are correct. Test the indication accuracy at three
points: the lower limit value, an intermediate value, and the upper limit val-
ue.
• Connect the external devices as shown in the following diagram.
• After verifying that the ZERO-CON is set to 0
°
C, set the STV’s output
voltage to produce a voltage equivalent to the test voltage.
Note
Always use the compensating conductors (the same kind that will be
used with the sensor being adjusted) to connect the ZERO-CON to
the CRT2-TS04T’s input terminals.
STV
INPUT
OUTPUT
CRT1-TS04T
Compensating
conductors
ZERO-CON
(0
°
C bath)
Input (+)
Input (–)
Содержание CRT1 - 10-2008
Страница 2: ...CRT1 Series CompoNet Slave Units and Repeater Unit Operation Manual Revised October 2008...
Страница 3: ...iv...
Страница 5: ...vi...
Страница 9: ...x...
Страница 15: ...xvi...
Страница 23: ...xxiv Conformance to EC Directives 6...
Страница 51: ...28 Slave Unit Models Section 1 2...
Страница 123: ...100 Connecting External I O for Slave Units Section 3 6...
Страница 365: ...342 Temperature Input Units Section 7 5...
Страница 381: ...358 Expansion Unit Specifications Section 8 2...
Страница 418: ...395 Repeater Unit Section 10 2 Dimensions 42 3 50 3 1 27 5 95 mm...
Страница 419: ...396 Repeater Unit Section 10 2...
Страница 424: ...401 CX Integrator Section 11 1...
Страница 575: ...552 Current Consumption Summary Appendix D 552...
Страница 581: ...558 Index...
Страница 583: ...560 Revision History...