448
Analog I/O Slave Unit Functions
Section 11-4
Setting Using the CX-Integrator
1,2,3...
1.
Turn ON the power supply to the CompoNet Slave Unit.
2.
Double-click the icon of the Slave Unit to set in the Network Configuration
Window to open the Configuration Window. (Alternatively, right-click the
icon and select
Parameters - Edit
from the pop-up menu.)
3.
Select the Tab Page for the output to be adjusted, and click the
Adjust-
ment
Button. (At this time, set the output range.)
Adjusting the Low Limit
4.
Output the value from the Master Unit that is equivalent to 0%. Always per-
form adjustment with the 0% value.
5.
Adjust the analog value that is output from the terminal using the Lower Ad-
justment slide bar, as shown in the following window. Repeat adjustments
until the correct 0% value is output from the output device. After compen-
sation is completed, click the
Fix Lower Adjusting Value
Button.
4 to 20 mA
3.2 to 4.8 mA
19.2 to 20.8 mA
0 to 20 mA
0.2 to 1.0 mA
19 to 21 mA
Output range
Low Limit
High Limit
Содержание CRT1 - 10-2008
Страница 2: ...CRT1 Series CompoNet Slave Units and Repeater Unit Operation Manual Revised October 2008...
Страница 3: ...iv...
Страница 5: ...vi...
Страница 9: ...x...
Страница 15: ...xvi...
Страница 23: ...xxiv Conformance to EC Directives 6...
Страница 51: ...28 Slave Unit Models Section 1 2...
Страница 123: ...100 Connecting External I O for Slave Units Section 3 6...
Страница 365: ...342 Temperature Input Units Section 7 5...
Страница 381: ...358 Expansion Unit Specifications Section 8 2...
Страница 418: ...395 Repeater Unit Section 10 2 Dimensions 42 3 50 3 1 27 5 95 mm...
Страница 419: ...396 Repeater Unit Section 10 2...
Страница 424: ...401 CX Integrator Section 11 1...
Страница 575: ...552 Current Consumption Summary Appendix D 552...
Страница 581: ...558 Index...
Страница 583: ...560 Revision History...