425
Analog I/O Slave Unit Functions
Section 11-4
5.
When User Scaling is selected, set the 0% value in the
Scaling Point (0%)
Field, and set the 100% value in the
Scaling Point (100%)
Field.
6.
For offset compensation, set the offset value in the
Scaling Offset
Field.
Either
Default Scaling
or
User Scaling
can be set in the
Scaling Type
Field.
7.
Return to the General Tab Page, click the
Transfer [PC to Unit]
Button to
download the data, and then click the
Reset
Button to reset the Unit.
8.
Click the
OK
Button and exit the window.