Features of CompoNet Slave Units
Section 1-1
Unit Conduction Time
Monitor
The total ON time of the Slave Unit's internal circuit power supply can be
stored. This value can be read using the CX-Integrator or explicit messages. A
value can also be set in the Slave Unit to enable obtaining notification of the
status if the total time reaches a set monitor value.
This data can be read or written by using the CX-Integrator.
Naming Units
The user can set any name for each Unit as a comment. The names are
stored in Slave Unit memory.
This data can be read or written by using the CX-Integrator.
Naming Connected
Devices
Any name can be set for each I/O contact (e.g., sensor or valve) connected to
a Slave Unit. The names are stored in Slave Unit memory.
This data can be read or written by using the CX-Integrator.
Network Power Voltage
Monitoring
The network power supply voltage (present, maximum, and minimum values)
can be stored in the Slave Unit memory. A monitor voltage can also be set in
the Slave Unit to enable notification of the status if the voltage drops to the
preset value.
These values can be set or read by using the CX-Integrator.
I/O Power Status Monitor
The I/O power status monitor function checks if the I/O power is ON or not,
and provides notification in a status area.
This data can be checked by using the CX-Integrator.
Communications Error
History Monitor
The previous four error records (communications error codes and the power
voltage when the error occurred) can be held in the Slave Unit memory.
This data can be read by using the CX-Integrator.
Input Filters
The Slave Units read input values multiple times during the set period to elim-
inate the effect of switch chattering and data omissions caused by noise. An
ON delay or OFF delay can also be implemented by using this function.
These settings are made by using the CX-Integrator.
Communications Error
Output Setting
The output value when a communications error occurs can be set for each
word of an Output Unit.
These settings are made by using the CX-Integrator.
Preventing Malfunctions
Caused by Inrush Current
at Startup
This function holds inputs from when the power is turned ON until the Unit sta-
bilizes, i.e., inputs are not received while the I/O power is OFF and for 100 ms
after the I/O power is turned ON. This contributes to eliminating input errors
caused by inrush current when the I/O power is turned ON.
These settings are made by using the CX-Integrator.
Power Short-circuit
Detection
The I/O power current is monitored. If an excessive current is detected, it is
assumed that a power short-circuit has occurred and the sensor power output
is turned OFF forcibly.
The status can be checked by using the LED indicators on the Slave Unit or
by using the CX-Integrator.
Load Short-circuit
Detection
The output load current is monitored. If an excessive current is detected, it is
assumed that an load short-circuit has occurred and the output is turned OFF
forcibly to prevent damage to the Unit's output circuit.
The status can be checked by using the LED indicators on the Slave Unit or
by using the CX-Integrator.
Removable Terminal Block
The terminal block can be removed.
Содержание CRT1 - 10-2008
Страница 2: ...CRT1 Series CompoNet Slave Units and Repeater Unit Operation Manual Revised October 2008...
Страница 3: ...iv...
Страница 5: ...vi...
Страница 9: ...x...
Страница 15: ...xvi...
Страница 23: ...xxiv Conformance to EC Directives 6...
Страница 51: ...28 Slave Unit Models Section 1 2...
Страница 123: ...100 Connecting External I O for Slave Units Section 3 6...
Страница 365: ...342 Temperature Input Units Section 7 5...
Страница 381: ...358 Expansion Unit Specifications Section 8 2...
Страница 418: ...395 Repeater Unit Section 10 2 Dimensions 42 3 50 3 1 27 5 95 mm...
Страница 419: ...396 Repeater Unit Section 10 2...
Страница 424: ...401 CX Integrator Section 11 1...
Страница 575: ...552 Current Consumption Summary Appendix D 552...
Страница 581: ...558 Index...
Страница 583: ...560 Revision History...