467
Temperature Input Unit Functions
Section 11-5
OFF Delay
The time until the Comparator Result Flag turns OFF can be extended. For
example, even if the Flag is ON momentarily, the OFF delay can be set so that
the Master Unit can receive notification of the Flag's status.
Setting Using CX-Integrator
1,2,3...
1.
Turn ON the power supply to the Temperature Input Unit.
2.
Double-click the icon of the Temperature Input Unit to be set in the Network
Configuration Window or right-click the icon and select
Parameter - Edit
.
The Configuration Window will be displayed.
3.
Click the tab for the input where comparator function is to be set, and select
the
Comparator
Check Box in the
Function Choice
Area.
4.
Click the
Comparator
Tab and set each of the alarm values. The example
here shows the setting for
Alarm Trip Point High (HH)
.
HH set value
Hysteresis width
OFF delay
HH Alarm Flag
Содержание CRT1 - 10-2008
Страница 2: ...CRT1 Series CompoNet Slave Units and Repeater Unit Operation Manual Revised October 2008...
Страница 3: ...iv...
Страница 5: ...vi...
Страница 9: ...x...
Страница 15: ...xvi...
Страница 23: ...xxiv Conformance to EC Directives 6...
Страница 51: ...28 Slave Unit Models Section 1 2...
Страница 123: ...100 Connecting External I O for Slave Units Section 3 6...
Страница 365: ...342 Temperature Input Units Section 7 5...
Страница 381: ...358 Expansion Unit Specifications Section 8 2...
Страница 418: ...395 Repeater Unit Section 10 2 Dimensions 42 3 50 3 1 27 5 95 mm...
Страница 419: ...396 Repeater Unit Section 10 2...
Страница 424: ...401 CX Integrator Section 11 1...
Страница 575: ...552 Current Consumption Summary Appendix D 552...
Страница 581: ...558 Index...
Страница 583: ...560 Revision History...