417
Word Slave Unit and Bit Slave Unit Functions
Section 11-3
Settings Using the CX-Integrator
1,2,3...
1.
Turn ON the power supply to the CompoNet Slave Unit.
2.
Double-click the icon of the Slave Unit to set in the Network Configuration
Window to open the Configuration Window. (Alternatively, right-click the
icon and select
Parameters - Edit
from the pop-up menu.)
3.
Click the
IN
Tab.
4.
Double-click the
I/O Comment
column for the terminal to be set. The Edit
Terminal Window will be displayed. Select
Time
for the Detection Mode,
enter the monitor value in the
Value
Field, and then click the
OK
Button.
5.
Return to the General Tab Page, click the
Transfer [PC to Unit]
Button to
download the data, and then click the
Reset
Button to reset the Unit.
6.
Click the OK Button and exit the window.
1.5 s
ON
OFF
Measured approx. every 1 s
Figure C
Содержание CRT1 - 10-2008
Страница 2: ...CRT1 Series CompoNet Slave Units and Repeater Unit Operation Manual Revised October 2008...
Страница 3: ...iv...
Страница 5: ...vi...
Страница 9: ...x...
Страница 15: ...xvi...
Страница 23: ...xxiv Conformance to EC Directives 6...
Страница 51: ...28 Slave Unit Models Section 1 2...
Страница 123: ...100 Connecting External I O for Slave Units Section 3 6...
Страница 365: ...342 Temperature Input Units Section 7 5...
Страница 381: ...358 Expansion Unit Specifications Section 8 2...
Страница 418: ...395 Repeater Unit Section 10 2 Dimensions 42 3 50 3 1 27 5 95 mm...
Страница 419: ...396 Repeater Unit Section 10 2...
Страница 424: ...401 CX Integrator Section 11 1...
Страница 575: ...552 Current Consumption Summary Appendix D 552...
Страница 581: ...558 Index...
Страница 583: ...560 Revision History...