518
CompoNet Explicit Messages
Appendix A
Setting and Reading for Analog Output Units
Explicit
message
Read
/write
Function Command
Response
Service
code
Class
ID
Instance
ID
Command data
Service data
Attribute
ID
Data
Analog Out-
put Value
Read
Read Reads analog output
values.
0E hex
0B hex 01 to 02
hex
03 hex
---
2 bytes
Output
Range Set-
ting
Write/
Read
Sets the output range.
4 to 20 mA: 0;
0 to 10 V: 1;
0 to 20 mA: 2;
−
10 to 10 V: 3;
0 to 5 V: 4;
1 to 5 V: 6
0E hex
0B hex 01 to 02
hex
07 hex
---
1 byte
Communi-
cations
Error Out-
put Setting
Write/
Read
Sets the communica-
tions error output value
for each output.
0: Hold last state
1: Low limit
2: High limit
3: Zero count
Write:
10 hex
Read:
0E hex
0B hex 01 to 02
hex
09 hex
1 byte
1 byte
Function
Setting
Write/
Read
Sets the function.
Scaling: 0;
Cumulative counter: 1
Write:
10 hex
Read:
0E hex
0B hex 01 to 02
hex
6E hex
1 byte
1 byte
Scaling
Type Set-
ting
Write/
Read
Default scaling: 0:
User scaling: 1
Write:
10 hex
Read:
0E hex
0B hex 01 to 02
hex
6F hex
1 byte
---
Scaling
Point 1 Set-
ting
Write/
Read
Sets a conversion value
as the 0% value for user
scaling.
Write:
10 hex
Read:
0E hex
0B hex 01 to 02
hex
70 hex
2 bytes
(
−
28000 to
28000)
2 bytes
(
−
28000 to
28000)
Scaling
Point 2 Set-
ting
Write/
Read
Sets a conversion value
as the 100% value for
user scaling.
Write:
10 hex
Read:
0E hex
0B hex 01 to 02
hex
71 hex
2 bytes
(
−
28000 to
28000)
2 bytes
(
−
28000 to
28000)
Offset
Compensa-
tion after
Scaling
Write/
Read
Compensates for scal-
ing errors with an offset
value.
Write:
10 hex
Read:
0E hex
0B hex 01 to 02
hex
72 hex
2 bytes
(
−
28000 to
28000)
2 bytes
(
−
28000 to
28000)
Cumulated
Value Read
Read/
Reset
Reads the cumulated
analog output value.
Read:
0E hex
Reset:
35 hex
0B hex 01 to 02
hex
91 hex
---
4 bytes
(
−
214748364.8
to
214748364.8)
Cumulative
Counter
Flag Read
Read Reads the cumulative
count status in the
Cumulative Counter
Flag in the area for
Generic Status Flags.
0: Counter overflow
1: Counter underflow
7: Set value overflow
Read:
0E hex
0B hex 01 to 02
hex
92 hex
---
1 byte
Содержание CRT1 - 10-2008
Страница 2: ...CRT1 Series CompoNet Slave Units and Repeater Unit Operation Manual Revised October 2008...
Страница 3: ...iv...
Страница 5: ...vi...
Страница 9: ...x...
Страница 15: ...xvi...
Страница 23: ...xxiv Conformance to EC Directives 6...
Страница 51: ...28 Slave Unit Models Section 1 2...
Страница 123: ...100 Connecting External I O for Slave Units Section 3 6...
Страница 365: ...342 Temperature Input Units Section 7 5...
Страница 381: ...358 Expansion Unit Specifications Section 8 2...
Страница 418: ...395 Repeater Unit Section 10 2 Dimensions 42 3 50 3 1 27 5 95 mm...
Страница 419: ...396 Repeater Unit Section 10 2...
Страница 424: ...401 CX Integrator Section 11 1...
Страница 575: ...552 Current Consumption Summary Appendix D 552...
Страница 581: ...558 Index...
Страница 583: ...560 Revision History...