515
CompoNet Explicit Messages
Appendix A
Explicit Messages for Analog I/O Slave Units
Reading DIP Switch Settings
Setting and Reading for Analog Input Units
Explicit
message
Read
/write
Function Command
Response
Service
code
Class
ID
Instance
ID
Command data
Service data
Attribute
ID
Data
DIP Switch
Status
Read
Read Reads the status of the
Input/Output Terminals
DIP switch.
0E hex
94 hex
01 hex
68 hex
---
1 byte
Explicit
message
Read
/write
Function Command
Response
Service
code
Class
ID
Instance
ID
Command data
Service data
Attribute
ID
Data
Analog
Data 1
Value
Read Reads the value for
Analog Data 1.
0E hex
0A hex
01 to 04
hex
03 hex
---
2 bytes
Analog
Data 2
Value
Read Reads the value for
Analog Data 2.
0E hex
0A hex
01 to 04
hex
65 hex
---
2 bytes
Setting the
Number of
AD Conver-
sion Points
Write/
Read
Sets the number of AD
conversion points.
Write:
10 hex
Read:
0E hex
0A hex
00 hex
64 hex
2 bytes
1 byte
Input
Range Set-
ting
Write/
Read
Sets the input range.
−
10 to 10 V: 0
0 to 5 V: 1
0 to 10 V: 2
4 to 20 mA: 3
1 to 5 V: 7
0 to 20 mA: 8
Write:
10 hex
Read:
0E hex
0A hex
01 to 04
hex
07 hex
1 byte
1 byte
Analog Sta-
tus Flag
Read
Read Reads the status of the
Analog Status Flags.
LL = 0; L = 1;
Pass signal = 2; H = 3;
HH = 4; Valley shot = 5;
Top shot = 6;
Disconnected line
detection = 7
0E hex
0A hex
01 to 04
hex
66 hex
---
1 byte
Analog
Data 1 Allo-
cation
Selection
Write/
Read
Selects the data allo-
cated to Analog Data 1.
Analog input value: 0
Peak value: 1,
Bottom value: 2,
Top value: 3,
Valley value: 4,
Rate of change value: 5
Write:
10 hex
Read:
0E hex
0A hex
01 to 04
hex
68 hex
1 byte
1 byte
Analog
Data 2 Allo-
cation
Selection
Write/
Read
Selects the data allo-
cated to Analog Data 2.
Analog input value: 0
Peak value: 1,
Bottom value: 2,
Top value: 3,
Valley value: 4,
Rate of change value: 5
Write:
10 hex
Read:
0E hex
0A hex
01 to 04
hex
69 hex
1 byte
1 byte
Содержание CRT1 - 10-2008
Страница 2: ...CRT1 Series CompoNet Slave Units and Repeater Unit Operation Manual Revised October 2008...
Страница 3: ...iv...
Страница 5: ...vi...
Страница 9: ...x...
Страница 15: ...xvi...
Страница 23: ...xxiv Conformance to EC Directives 6...
Страница 51: ...28 Slave Unit Models Section 1 2...
Страница 123: ...100 Connecting External I O for Slave Units Section 3 6...
Страница 365: ...342 Temperature Input Units Section 7 5...
Страница 381: ...358 Expansion Unit Specifications Section 8 2...
Страница 418: ...395 Repeater Unit Section 10 2 Dimensions 42 3 50 3 1 27 5 95 mm...
Страница 419: ...396 Repeater Unit Section 10 2...
Страница 424: ...401 CX Integrator Section 11 1...
Страница 575: ...552 Current Consumption Summary Appendix D 552...
Страница 581: ...558 Index...