497
Troubleshooting
Section 12-2
All models other than
Analog I/O Slave
Units
The Maintenance Counter
returned to 0.
• The Maintenance Counter will
return to 0 if the Unit is reset.
• The Maintenance Counter will
always return to 0 when the
setting is switched between
the Total ON Time Monitor
Function and the Contact
Operation Monitor Function.
---
Some functions do not change
even after parameters have
been edited or set.
The functions that have been
changed are enabled only after
the power is cycled.
Cycle the power or reset the
CX-Integrator.
The Maintenance Counter is
not counting even though out-
puts are turned ON.
The I/O power supply is OFF.
Check that the I/O power sup-
ply is turned ON.
Slave Units to which
Expansion Units can
be mounted
I/O communications stopped
after mounting or removing an
Expansion Unit and turning ON
the power.
The number of I/O points
increase or decrease when
Expansion Units are mounted
or removed. The number of I/O
points may not match the I/O
table registered in the Master
Unit.
Change the Master Unit I/O
table settings.
The MS indicator lights red
after mounting or removing an
Expansion Unit online.
Expansion Units cannot be
mounted or removed online.
Turn OFF the power before
mounting or removing Expan-
sion Units.
Slave Units with
Operation Time Moni-
tor Function
The Operation Time Monitor
does not show the expected
values.
• If the input filter is set, there is
a delay with the ON or OFF
time.
• The operation time ON or
OFF edge selection may not
be on the intended setting.
• The selected operation time
combination is not supported.
If the operation time monitor
does not show the expected
values, the settings may be
different from the intended
settings. The accuracy is
±
6
ms.
• Use the Operation Time Mon-
itor function considering the
filter setting or set the filter
constant to 0 ms.
• Check the operation time
combination set for Slave
Units for which the operation
time edge can be set.
The status flag for the Opera-
tion Time Monitor value turns
ON and OFF.
The Operation Time Flag is
refreshed every measurement
cycle, after the operation time
is compared with the monitor
value. The Operation Time
Flag turns ON for one cycle
and turns OFF, if the operation
time drops below the monitor
value at refreshing. There is
another flag that holds the con-
tents of monitor value
exceeded flags.
---
Slave Units with out-
puts
Cannot hold outputs when
communication errors occur.
The Unit is set to clear outputs
for communications errors.
Change the setting to hold out-
puts for communications
errors.
Cannot clear outputs when
communication errors occur.
The Unit is set to hold outputs
for communications errors.
Change the setting to clear
outputs for communications
errors.
Slave Units with
inputs
There is a delay with the ON
and OFF timing for input val-
ues.
An input filter may be set.
Set the input filter value to 0.
Alternatively, change the input
filter to an appropriate value.
Model
Problem
Cause
Possible correction
Содержание CRT1 - 10-2008
Страница 2: ...CRT1 Series CompoNet Slave Units and Repeater Unit Operation Manual Revised October 2008...
Страница 3: ...iv...
Страница 5: ...vi...
Страница 9: ...x...
Страница 15: ...xvi...
Страница 23: ...xxiv Conformance to EC Directives 6...
Страница 51: ...28 Slave Unit Models Section 1 2...
Страница 123: ...100 Connecting External I O for Slave Units Section 3 6...
Страница 365: ...342 Temperature Input Units Section 7 5...
Страница 381: ...358 Expansion Unit Specifications Section 8 2...
Страница 418: ...395 Repeater Unit Section 10 2 Dimensions 42 3 50 3 1 27 5 95 mm...
Страница 419: ...396 Repeater Unit Section 10 2...
Страница 424: ...401 CX Integrator Section 11 1...
Страница 575: ...552 Current Consumption Summary Appendix D 552...
Страница 581: ...558 Index...
Страница 583: ...560 Revision History...