141
Units with Screw Terminal Blocks
Section 5-3
5-3-8
Sixteen-point Output Units (2-tier Terminal Block with Relay
Outputs)
CRT1-ROS16
Common Specifications
Relay Output Section Specifications (per Output)
Note
(1) With a current of between 2 and 3 A (8 to 10 A per common), either en-
sure that the number of points per common that simultaneously turn ON
does not exceed 4 or ensure that the temperature does not exceed 45
°
C.
There are no restrictions if the current does not exceed 2 A (8 A per com-
mon).
Item
Specification
Communications power supply voltage
14 to 26.4 VDC
Noise immunity
Conforms to IEC 61000-4-4, 2 kV (power line).
Vibration resistance
10 to 55 Hz with double-amplitude of 0.7 mm
Shock resistance
100 m/s
2
(3 times in 6 directions on 3 axes)
Dielectric strength
500 VAC (between isolated circuits)
Insulation resistance
20 M
Ω
min. (between isolated circuits)
Ambient operating temperature
−
10 to 55
°
C
Ambient operating humidity
25% to 85% (with no condensation)
Ambient operating atmosphere
No corrosive gases
Storage temperature
−
25 to 65
°
C
Storage humidity
25% to 85% (with no condensation)
Terminal block screws tightening torque
M3 wiring screws: 0.5 N
⋅
m
M3 mounting screws: 0.5 N
⋅
m
Item
Specification
Model
CRT1-ROS16
I/O capacity
16 outputs
Mounted Relays
DRTA-NY5W-K (5 VDC)
Rated load
Resistive load
250 VAC, 2 A, common: 8 A
30 VDC, 2 A, common: 8 A
Rated ON current
3 A
Maximum contact voltage
250 VAC, 125 VDC
Maximum contact current
3 A
Maximum switching capacity
750 VA AC, 90 W DC
Minimum applicable load (reference value) 5 VDC, 1 mA
Mechanical service life
20,000,000 operations min.
Electrical service life
100,000 operations min.
Installation method
DIN Track
Communications power supply current
consumption
155 mA max. for 24-VDC power supply voltage
255 mA max. for 14-VDC power supply voltage
Output hold for communications errors
Select either hold or clear from CX-Integrator.
Weight
260 g max.
Содержание CRT1 - 10-2008
Страница 2: ...CRT1 Series CompoNet Slave Units and Repeater Unit Operation Manual Revised October 2008...
Страница 3: ...iv...
Страница 5: ...vi...
Страница 9: ...x...
Страница 15: ...xvi...
Страница 23: ...xxiv Conformance to EC Directives 6...
Страница 51: ...28 Slave Unit Models Section 1 2...
Страница 123: ...100 Connecting External I O for Slave Units Section 3 6...
Страница 365: ...342 Temperature Input Units Section 7 5...
Страница 381: ...358 Expansion Unit Specifications Section 8 2...