449
Analog I/O Slave Unit Functions
Section 11-4
Adjusting the High Limit
6.
Output the value from the Master Unit that is equivalent to the Output Unit’s
maximum (100%) value. Adjustment using the 100% value is highly recom-
mended, but adjustment can be performed using a lower value.
7.
Adjust the analog value that is output from the terminal using the High Ad-
justment slide bar, as shown in the following window. Repeat adjustments
until the correct 100% value is output from the output device. After com-
pensation is completed, click the
Fix Upper Adjusting Value
Button.
To return to the default settings, click the
Default Setting
Button.
8.
Click the
Close
Button to close the Adjustment Window.
9.
Return to the General Tab Page, click the
Transfer [PC to Unit
] Button to
download the data, and then click the
Reset
Button to reset the Unit.
10. Click the
OK
Button and exit the window.
Note
If the Low Limit adjustment is not performed for the 0% value, a discrepancy
will occur when the High Limit is adjusted. Therefore, always adjust the Low
Limit for Output Units before adjusting the High Limit.
Cumulative Counter
The cumulative counter calculates an approximation to the integral of analog
output values over time. The cumulated value can be calculated in “count
hours” (by selecting “hours”) or “count minutes” (by selecting “minutes”). The
count value is the analog output value in the industry unit obtained after scal-
ing. For example, 100.0 count hours indicates a value equivalent to an analog
output value of 100 counts continuing for one hour. The counter range for a
two-word area (four bytes) for count hours or count minutes is –214,748,364.8
Содержание CRT1 - 10-2008
Страница 2: ...CRT1 Series CompoNet Slave Units and Repeater Unit Operation Manual Revised October 2008...
Страница 3: ...iv...
Страница 5: ...vi...
Страница 9: ...x...
Страница 15: ...xvi...
Страница 23: ...xxiv Conformance to EC Directives 6...
Страница 51: ...28 Slave Unit Models Section 1 2...
Страница 123: ...100 Connecting External I O for Slave Units Section 3 6...
Страница 365: ...342 Temperature Input Units Section 7 5...
Страница 381: ...358 Expansion Unit Specifications Section 8 2...
Страница 418: ...395 Repeater Unit Section 10 2 Dimensions 42 3 50 3 1 27 5 95 mm...
Страница 419: ...396 Repeater Unit Section 10 2...
Страница 424: ...401 CX Integrator Section 11 1...
Страница 575: ...552 Current Consumption Summary Appendix D 552...
Страница 581: ...558 Index...
Страница 583: ...560 Revision History...