487
Temperature Input Unit Functions
Section 11-5
CX-Integrator
Actual adjustments are made from the CX-Integrator.
Adjustment Device
Connection Diagram
Connect the six-dial resistance box to the input terminals.
Connect them to the input terminals for the required input from input 0 to 3.
Note
(1) When connecting the six-dial resistance box, use a cable with the same
gauge as the one that will be used for operation.
(2) The personal computer (CX-Integrator) is connected through CompoNet
in the above diagram. If a CS1W-CRM21 or CJ1W-CRM21 Master Unit is
being used, it can be connected through the Master Unit using a periph-
eral bus connection to adjust the Temperature Input Unit.
Input Terminal
Connections
Checking the Wiring and
Making Adjustments
Adjusting the Upper and Lower Limit Values
1,2,3...
1.
Set the resistance value on the six-dial resistance box equivalent to the
test value and properly wire the box to the input of the Temperature Input
Unit that is being adjusted.
2.
If the correct resistance cannot be obtained, properly wire the digital mul-
timeter to the six-dial resistance box and measure the resistance.
3.
Connect the CX-Integrator to the CompoNet network and go online.
4.
Upload settings to the CX-Integrator.
5.
Turn ON the power supplies of all Units, including the Temperature Input
Unit to be adjusted. Wait approximately 30 minutes for the Temperature In-
put Unit's internal temperature to stabilize.
6.
Double-click the icon of the Temperature Input Unit to be set in the Network
Configuration Window or right-click the icon and select
Parameters - Edit
.
The Configuration Window will be displayed.
CRT1-TS04P
CX-Integrator
Six-dial resistance box
Connect to the input terminals of
the input being adjusted.
Precision digital multimeter (DMM)
Use to confirm that the six-dial resistance
box is providing an accurate resistance.
CompoNet
0A
1A
NC
NC
NC
NC
NC
NC
0B
1B
2B
3B
1B
0B
2B
2A
3A
3B
Six-dial resistance box
DMM
Содержание CRT1 - 10-2008
Страница 2: ...CRT1 Series CompoNet Slave Units and Repeater Unit Operation Manual Revised October 2008...
Страница 3: ...iv...
Страница 5: ...vi...
Страница 9: ...x...
Страница 15: ...xvi...
Страница 23: ...xxiv Conformance to EC Directives 6...
Страница 51: ...28 Slave Unit Models Section 1 2...
Страница 123: ...100 Connecting External I O for Slave Units Section 3 6...
Страница 365: ...342 Temperature Input Units Section 7 5...
Страница 381: ...358 Expansion Unit Specifications Section 8 2...
Страница 418: ...395 Repeater Unit Section 10 2 Dimensions 42 3 50 3 1 27 5 95 mm...
Страница 419: ...396 Repeater Unit Section 10 2...
Страница 424: ...401 CX Integrator Section 11 1...
Страница 575: ...552 Current Consumption Summary Appendix D 552...
Страница 581: ...558 Index...
Страница 583: ...560 Revision History...