85
Power Supply Wiring
Section 3-5
The allowable currents for cables and connectors are given below.
Allowable Currents for
Cables
Select the communications cable so that the total current consumption of all
Slave Units does not exceed the allowable current of the cable.
Allowable Currents for
Connectors
There are limits to the allowable current for the communications power supply
connectors on the Master Unit and Repeater Units, Flat Connector Sockets,
and Flat Connector Plugs. Do not allow the current flow where these connec-
tors are used to exceed the allowable current.
Voltage Drop
Cable Voltage Drop
The voltage drop must be considered so that the power supply voltage at the
Slave Unit that is the farthest from the power supply will still be within the
allowable power supply range.
The voltage drop is expressed by the following formula.
If the voltage drop is too large and power cannot be supplied to the farthest
Slave Unit within the allowable range, add a Repeater Unit and supply power
from the Repeater Unit.
Master
Unit
Power
supply,
24 VDC
Slave Unit
current con-
sumption I
1
Terminating
Resistor
Slave Unit
current con-
sumption I
2
Slave Unit
current con-
sumption I
3
Flat Connector Plug: 5 A max. (UL: 4 A)
Flat Connector Socket: 5 A max. (UL: 4A)
Cable
Slave Unit
current con-
sumption I
n
(a)
Cable allowable current
≥
I
1
+ I
2
+ I
3
+ · · · · I
n
(For the allowable cable current for “a” in the above diagram)
Name
Model
Allowable
current
Communications power supply connectors on CS/
CJ-Master Units
CS1W-CRM21
5 A
(UL: 4 A)
CJ1W-CRM21
Communications power supply connector on
Repeater Unit
CRS1-RPT01
Flat Connector Sockets
DCN4-TR4
DCN5-TR4
Flat Connector Plugs
DCN4-BR4
DCN5-BR4
Multidrop Connector
DCN4-MD4
Voltage drop (V) = Current (A)
×
Cable conductor resistance (
Ω
/m)
×
Cable length
(m)
×
2
Содержание CRT1 - 10-2008
Страница 2: ...CRT1 Series CompoNet Slave Units and Repeater Unit Operation Manual Revised October 2008...
Страница 3: ...iv...
Страница 5: ...vi...
Страница 9: ...x...
Страница 15: ...xvi...
Страница 23: ...xxiv Conformance to EC Directives 6...
Страница 51: ...28 Slave Unit Models Section 1 2...
Страница 123: ...100 Connecting External I O for Slave Units Section 3 6...
Страница 365: ...342 Temperature Input Units Section 7 5...
Страница 381: ...358 Expansion Unit Specifications Section 8 2...
Страница 418: ...395 Repeater Unit Section 10 2 Dimensions 42 3 50 3 1 27 5 95 mm...
Страница 419: ...396 Repeater Unit Section 10 2...
Страница 424: ...401 CX Integrator Section 11 1...
Страница 575: ...552 Current Consumption Summary Appendix D 552...
Страница 581: ...558 Index...
Страница 583: ...560 Revision History...