507
CompoNet Explicit Messages
Appendix A
Explicit Messages for Digital I/O Slave Units
Setting and Monitoring Inputs
Explicit
message
Read/
write
Function Command
Response
Service
code
Class
ID
Instance
ID
Command data
Service data
Attribute
ID
Data
Terminal
Mainte-
nance Infor-
mation
Monitor
Mode
Read
Reads the monitor
mode for maintenance
information of the input
(No. 1 to 32) specified
by the Instance ID.
0E hex
08 hex
01 to 20
hex
65 hex
---
1 byte
00 hex: Total ON
time mode
01 hex: Contact
operation
counter mode
Write
Writes the monitor
mode for maintenance
information of the input
(No. 1 to 32) specified
by the Instance ID.
10 hex
08 hex
01 to 20
hex
65 hex
1 byte
00 hex: Total
ON time
mode
01 hex: Con-
tact opera-
tion counter
mode
---
Set Value
for Input
Total ON
Time or
Contact
Operation
Counter
Read
Reads the set value for
the total ON time (unit:
s) or number of contact
operations (unit: opera-
tions) of the input (No.
1 to 32) specified by
the Instance ID.
0E hex
08 hex
01 to 20
hex
68 hex
---
4 bytes
00000000 to
FFFFFFFF hex
(0 to
4294967295)
Write
Writes the set value for
the total ON time (unit:
s) or number of contact
operations (unit: opera-
tions) of the input (No.
1 to 32) specified by
the Instance ID.
10 hex
08 hex
01 to 20
hex
68 hex
4 bytes
00000000 to
FFFFFFFF
hex
(0 to
4294967295)
---
Input Total
ON Time or
Contact
Operation
Counter
Read
Read
Reads the total ON
time (unit: s) or number
of contact operations
(unit: operations) for
the input (No. 1 to 32)
specified by the
Instance ID.
0E hex
08 hex
01 to 20
hex
66 hex
---
4 bytes
00000000 to
FFFFFFFF hex
(0 to
4294967295)
Input Total
ON Time or
Contact
Operation
Counter
Reset
Reset
Resets the total ON
time (unit: s) or number
of contact operations
(unit: operations) for
the input (No. 1 to 32)
specified by the
Instance ID.
05 hex
08 hex
01 to 20
hex
66 hex
---
---
Monitor
Status for
Input Total
ON Time or
Contact
Operation
Counter
Read
Read
Reads the monitor sta-
tus for total ON time or
number of contact
operations for the input
(No. 1 to 32) specified
by the Instance ID.
0E hex
08 hex
01 to 20
hex
67 hex
---
1 byte
00 hex: Within
range
01 hex: Out of
range (over the
monitor value)
Содержание CRT1 - 10-2008
Страница 2: ...CRT1 Series CompoNet Slave Units and Repeater Unit Operation Manual Revised October 2008...
Страница 3: ...iv...
Страница 5: ...vi...
Страница 9: ...x...
Страница 15: ...xvi...
Страница 23: ...xxiv Conformance to EC Directives 6...
Страница 51: ...28 Slave Unit Models Section 1 2...
Страница 123: ...100 Connecting External I O for Slave Units Section 3 6...
Страница 365: ...342 Temperature Input Units Section 7 5...
Страница 381: ...358 Expansion Unit Specifications Section 8 2...
Страница 418: ...395 Repeater Unit Section 10 2 Dimensions 42 3 50 3 1 27 5 95 mm...
Страница 419: ...396 Repeater Unit Section 10 2...
Страница 424: ...401 CX Integrator Section 11 1...
Страница 575: ...552 Current Consumption Summary Appendix D 552...
Страница 581: ...558 Index...
Страница 583: ...560 Revision History...