Temperature Input Unit Functions
Section 11-5
7.
Click the tab for the input that will be adjusted and click the
Adjustment
Button.
8.
Adjust the lower limit value. Input 18
Ω
from the six-dial resistance box to
the Temperature Input Unit's input terminals. Wait at least 1 minute for the
input to stabilize.
9.
Click the
Fix Lower Adjusting Value
Button in the Adjustment Window to
write the adjustment value.
10. Adjust the upper limit value. Input the resistance from the six-dial resis-
tance box. Refer to the following table for the appropriate resistance to in-
put. Wait at least 1 minute for the input to stabilize.
11. Click the
Fix Upper Adjusting Value
Button to write the adjustment value.
Type
Input resistance for upper
limit adjustment
PT100 (
−
200 to 850
°
C)
390
Ω
PT100 (
−
200 to 200
°
C)
180
Ω
Содержание CRT1 - 10-2008
Страница 2: ...CRT1 Series CompoNet Slave Units and Repeater Unit Operation Manual Revised October 2008...
Страница 3: ...iv...
Страница 5: ...vi...
Страница 9: ...x...
Страница 15: ...xvi...
Страница 23: ...xxiv Conformance to EC Directives 6...
Страница 51: ...28 Slave Unit Models Section 1 2...
Страница 123: ...100 Connecting External I O for Slave Units Section 3 6...
Страница 365: ...342 Temperature Input Units Section 7 5...
Страница 381: ...358 Expansion Unit Specifications Section 8 2...
Страница 418: ...395 Repeater Unit Section 10 2 Dimensions 42 3 50 3 1 27 5 95 mm...
Страница 419: ...396 Repeater Unit Section 10 2...
Страница 424: ...401 CX Integrator Section 11 1...
Страница 575: ...552 Current Consumption Summary Appendix D 552...
Страница 581: ...558 Index...
Страница 583: ...560 Revision History...