Analog I/O Slave Unit Functions
Section 11-4
5.
Return to the General Tab Page, click the
Transfer [PC to Unit]
Button to
download the data, and then click the
Reset
Button to reset the Unit.
6.
Click the
OK
Button and exit the window.
Comparator
Four values can be set in the Slave Unit, and compared with the Analog Data
values.
The four set values are the Alarm Trip Point High (HH), the Warning Trip Point
High (H), the Warning Trip Point Low (L), and the Alarm Trip Point Low (LL).
When the analog data value exceeds the set value, the Comparator Result
Flag in the area for Analog Status Flags turns ON. If an alarm does not occur,
the Normal Flag (pass signal) turns ON.
Note
When the analog input value changes earlier than the conversion cycle, the
High Limit alarm may turn ON without the Normal Flag (pass signal) turning
ON for the Low Limit alarm. Configure ladder programs to prevent this occur-
ring.
Set values
HH
H
L
LL
Comparator Result Flag
(in Analog Status Flags)
ON/OFF
HH alarm
H alarm
Normal Flag
(Pass signal)
L alarm
LL alarm
Содержание CRT1 - 10-2008
Страница 2: ...CRT1 Series CompoNet Slave Units and Repeater Unit Operation Manual Revised October 2008...
Страница 3: ...iv...
Страница 5: ...vi...
Страница 9: ...x...
Страница 15: ...xvi...
Страница 23: ...xxiv Conformance to EC Directives 6...
Страница 51: ...28 Slave Unit Models Section 1 2...
Страница 123: ...100 Connecting External I O for Slave Units Section 3 6...
Страница 365: ...342 Temperature Input Units Section 7 5...
Страница 381: ...358 Expansion Unit Specifications Section 8 2...
Страница 418: ...395 Repeater Unit Section 10 2 Dimensions 42 3 50 3 1 27 5 95 mm...
Страница 419: ...396 Repeater Unit Section 10 2...
Страница 424: ...401 CX Integrator Section 11 1...
Страница 575: ...552 Current Consumption Summary Appendix D 552...
Страница 581: ...558 Index...
Страница 583: ...560 Revision History...