465
Temperature Input Unit Functions
Section 11-5
4.
Click the
Rate of Change
Tab and input the desired value for the sampling
cycle.
5.
Return to the
General
Tab Page, click the
Transfer [PC to Unit]
Button to
download the data, and then click the
Reset
Button to reset the Unit.
6.
Click the
OK
Button and exit the window.
11-5-7 Comparator
When the High High Limit, High Limit, Low Low Limit, and Low Limit are set in
the Unit, a status flag will be turned ON when a value exceeds the set range.
The four set values are High High Limit (HH), High Limit (H), Low Low Limit
(LL), and Low Limit (L). The values are compared with those in Temperature
Data 1. (The comparator function cannot be used with Temperature Data 2.)
The setting range is
−
415,000 to 415,000.
When any of these values is exceeded, the Comparator Result Flag in the
area for Temperature Status Flags is turned ON. If an alarm has not occurred,
the Normal Flag (pass signal) will be ON.
Содержание CRT1 - 10-2008
Страница 2: ...CRT1 Series CompoNet Slave Units and Repeater Unit Operation Manual Revised October 2008...
Страница 3: ...iv...
Страница 5: ...vi...
Страница 9: ...x...
Страница 15: ...xvi...
Страница 23: ...xxiv Conformance to EC Directives 6...
Страница 51: ...28 Slave Unit Models Section 1 2...
Страница 123: ...100 Connecting External I O for Slave Units Section 3 6...
Страница 365: ...342 Temperature Input Units Section 7 5...
Страница 381: ...358 Expansion Unit Specifications Section 8 2...
Страница 418: ...395 Repeater Unit Section 10 2 Dimensions 42 3 50 3 1 27 5 95 mm...
Страница 419: ...396 Repeater Unit Section 10 2...
Страница 424: ...401 CX Integrator Section 11 1...
Страница 575: ...552 Current Consumption Summary Appendix D 552...
Страница 581: ...558 Index...
Страница 583: ...560 Revision History...