361
Allocating I/O Data
Section 9-2
Alarm Status Area
The Bit Slave Unit’s Alarm Status Area contains the following 16 bits. These
bits indicate serious errors in the Unit.
9-2
Allocating I/O Data
Bit Slave Units are allocated node address areas in units of two points (two
bits).
• Input Units and Output Units
Units with two points are allocated two bits (the node address set for the
Unit).
Units with four points are allocated four bits (the node address set for the
Unit and the next node address area).
• I/O Units
Units are allocated two words (the input and output node address areas).
Two-point Input Units
Four-point Input Units
Two-point Output Units
Bit
Content
Description
0
Reserved
---
1
EEPROM Data Error Flag
OFF: Normal
ON: Error occurred
Turns ON when there is an error in
the EEPROM data.
2
Reserved
---
3
Reserved
---
4
Reserved
---
5
Reserved
---
6
Reserved
---
7
Reserved
---
8
Reserved
---
9
Reserved
---
10
Power Short-circuit Detection Flag
OFF: Normal
ON: Short-circuit
Turns ON when there is a short in the
power supply connection to the con-
nected devices, including wiring mis-
takes and connected device failure.
11
Load Short-circuit Detection Flag
OFF: Normal
ON: Short-circuit
Turns ON when there is a short in the
load connection, including wiring mis-
takes and connected device failure.
12
Reserved
---
13
Reserved
---
14
Reserved
---
15
Reserved
---
Bit Input Area
1
0
Bit Input Area
3
2
1
0
Bit Output Area
1 0
Содержание CRT1 - 10-2008
Страница 2: ...CRT1 Series CompoNet Slave Units and Repeater Unit Operation Manual Revised October 2008...
Страница 3: ...iv...
Страница 5: ...vi...
Страница 9: ...x...
Страница 15: ...xvi...
Страница 23: ...xxiv Conformance to EC Directives 6...
Страница 51: ...28 Slave Unit Models Section 1 2...
Страница 123: ...100 Connecting External I O for Slave Units Section 3 6...
Страница 365: ...342 Temperature Input Units Section 7 5...
Страница 381: ...358 Expansion Unit Specifications Section 8 2...
Страница 418: ...395 Repeater Unit Section 10 2 Dimensions 42 3 50 3 1 27 5 95 mm...
Страница 419: ...396 Repeater Unit Section 10 2...
Страница 424: ...401 CX Integrator Section 11 1...
Страница 575: ...552 Current Consumption Summary Appendix D 552...
Страница 581: ...558 Index...
Страница 583: ...560 Revision History...