393
Repeater Unit
Section 10-2
Component Names and Functions
Indicator Section
Communications
Indicators
The communications indicators have the following meanings.
MS (Module Status): Indicates the status of the node with a two-color LED
(green/red).
NS (Network Status): Indicates the status of communications with a two-color
LED (green/red).
Note
When flashing, indicators are lit for 0.5 s and not lit for 0.5 s.
PORT1
PORT2
CRS1
CRS1-RPT01
RPT01
RPT
NODE ADR
NETWORK POWER SUPPLY
BS+
BS-
X10
[0-63]
X1
MS NS
RPT
RPT
DC24V
INPUT
012
3
45678
9
012
3
45678
9
Communications indicators: MS and NS
Node address switches:
×
10 and
×
1 (from left)
Port 2:
Downstream port
communications connector
Downstream port
communications power supply
connector (removable)
Port 1:
Upstream port communications
Name
Indicator status
Status
Meaning
MS
Lit green.
Normal status
The Unit is operating normally.
Flashing
green.
---
---
Lit red.
Fatal error
A hardware error has occurred in the Unit. The watchdog
timer has timed-out.
Flashing red.
Non-fatal error
There is an error in the settings.
An EEPROM checksum error has occurred.
Not lit.
Power OFF/Startup
The power supply is OFF, the Unit is being reset, or the Unit
is being initialized.
NS
Lit green.
Online and participating
Normal communications are in progress and the node is par-
ticipating in the network.
Flashing
green.
Online but not participat-
ing
Normal communications are in progress but the node is not
yet participating in the network.
Lit red.
Fatal communications
error
The address is set out of range or the same address has
been set for more than one node.
Flashing red.
Non-fatal communications
error
Polling has timed out. The network has timed out.
Not lit.
Power OFF/Baud rate not
yet detected.
The power supply is OFF or the baud rate has not been
detected.
Содержание CRT1 - 10-2008
Страница 2: ...CRT1 Series CompoNet Slave Units and Repeater Unit Operation Manual Revised October 2008...
Страница 3: ...iv...
Страница 5: ...vi...
Страница 9: ...x...
Страница 15: ...xvi...
Страница 23: ...xxiv Conformance to EC Directives 6...
Страница 51: ...28 Slave Unit Models Section 1 2...
Страница 123: ...100 Connecting External I O for Slave Units Section 3 6...
Страница 365: ...342 Temperature Input Units Section 7 5...
Страница 381: ...358 Expansion Unit Specifications Section 8 2...
Страница 418: ...395 Repeater Unit Section 10 2 Dimensions 42 3 50 3 1 27 5 95 mm...
Страница 419: ...396 Repeater Unit Section 10 2...
Страница 424: ...401 CX Integrator Section 11 1...
Страница 575: ...552 Current Consumption Summary Appendix D 552...
Страница 581: ...558 Index...
Страница 583: ...560 Revision History...