509
CompoNet Explicit Messages
Appendix A
Setting and Monitoring Operation Time
Note
Refer to the note on page 525.
Explicit
message
Read
/write
Function Command
Response
Service
code
Class
ID
Instance
ID
Command data
Service
data
Attribute
ID
Data
Operation
Time Moni-
tor Status
Read
Read Reads the monitor sta-
tus for the time (unit: ms)
from the start point trig-
ger until the end point
trigger specified by the
Instance ID (No. 1 to 8).
0E hex
97 hex
01 to 08
hex
66 hex
---
1 byte
00 hex:
Threshold
not passed
01 hex:
Threshold
passed
Operation
Time Moni-
tor Setting
Read Reads the setting for the
time (unit: ms) from the
start point trigger until
the end point trigger
specified by the Instance
ID (No. 1 to 8).
0E hex
97 hex
01 to 08
hex
67 hex
---
2 bytes
(See note.)
Write
Writes the setting for the
time (unit: ms) from the
start point trigger until
the end point trigger
specified by the Instance
ID (No. 1 to 8).
10 hex
97 hex
01 to 08
hex
67 hex
---
2 bytes
(See note.)
Operation
Time Moni-
tor Peak
Value Read
Read Reads the peak value for
the time (unit: ms) from
the start point trigger
until the end point trigger
specified by the Instance
ID (No. 1 to 8).
0E hex
97 hex
01 to 08
hex
68 hex
---
2 bytes
0000 to
FFFF hex
(0 to 65535)
Operation
Time Moni-
tor Peak
Value
Reset
Reset Resets to the present
value the peak value for
the time (unit: ms) from
the start point trigger
until the end point trigger
specified by the Instance
ID (No. 1 to 8)
05 hex
97 hex
01 to 08
hex
68 hex
---
---
Operation
Time Moni-
tor History
Read Reads the monitor his-
tory for the time (unit:
ms) from the start point
trigger until the end point
trigger specified by the
Instance ID (No. 1 to 8).
0E hex
97 hex
01 to 08
hex
6D hex
---
1 byte
00 hex:
Value not
exceeded
01 hex:
Value
exceeded
Operation
Time Moni-
tor History
Reset
Reset Resets the monitor his-
tory for the time (unit:
ms) from the start point
trigger until the end point
trigger specified by the
Instance ID (No. 1 to 8)
to 0.
05 hex
97 hex
01 to 08
hex
6D hex
---
---
Содержание CRT1 - 10-2008
Страница 2: ...CRT1 Series CompoNet Slave Units and Repeater Unit Operation Manual Revised October 2008...
Страница 3: ...iv...
Страница 5: ...vi...
Страница 9: ...x...
Страница 15: ...xvi...
Страница 23: ...xxiv Conformance to EC Directives 6...
Страница 51: ...28 Slave Unit Models Section 1 2...
Страница 123: ...100 Connecting External I O for Slave Units Section 3 6...
Страница 365: ...342 Temperature Input Units Section 7 5...
Страница 381: ...358 Expansion Unit Specifications Section 8 2...
Страница 418: ...395 Repeater Unit Section 10 2 Dimensions 42 3 50 3 1 27 5 95 mm...
Страница 419: ...396 Repeater Unit Section 10 2...
Страница 424: ...401 CX Integrator Section 11 1...
Страница 575: ...552 Current Consumption Summary Appendix D 552...
Страница 581: ...558 Index...
Страница 583: ...560 Revision History...