312
Analog Output Slave Units
Section 6-5
■
Output 0 Range
■
Output 1 Range
Setting Using the CX-
Integrator
Use the following procedure to set the output range for each output using the
CX-Integrator.
1,2,3...
1.
Turn ON the power to the CompoNet Slave Unit.
2.
Double-click the icon of the Analog Output Unit to set in the Network Con-
figuration Window to open the Configuration Window. (Alternatively, right-
click the icon and select
Parameters - Edit
from the pop-up menu.)
3.
Select the Tab Page for the output where the range is to be changed.
4.
Click the
Output Range
Field, and select the desired range.
5.
Return to the General Tab Page, click the
Transfer [PC to Unit]
Button to
download the data, and then click the
Reset
Button to reset the Unit.
6.
Click the
OK
Button and exit the window.
Signal range
Pin 1
Pin 2
Pin 3
0 to 5 V
OFF
OFF
OFF
1 to 5 V
ON
OFF
OFF
0 to 10 V
OFF
ON
OFF
–10 to 10 V
ON
ON
OFF
4 to 20 mA
OFF
OFF
ON
0 to 20 mA
ON
OFF
ON
Signal range
Pin 4
Pin 5
Pin 6
0 to 5 V
OFF
OFF
OFF
1 to 5 V
ON
OFF
OFF
0 to 10 V
OFF
ON
OFF
–10 to 10 V
ON
ON
OFF
4 to 20 mA
OFF
OFF
ON
0 to 20 mA
ON
OFF
ON
Содержание CRT1 - 10-2008
Страница 2: ...CRT1 Series CompoNet Slave Units and Repeater Unit Operation Manual Revised October 2008...
Страница 3: ...iv...
Страница 5: ...vi...
Страница 9: ...x...
Страница 15: ...xvi...
Страница 23: ...xxiv Conformance to EC Directives 6...
Страница 51: ...28 Slave Unit Models Section 1 2...
Страница 123: ...100 Connecting External I O for Slave Units Section 3 6...
Страница 365: ...342 Temperature Input Units Section 7 5...
Страница 381: ...358 Expansion Unit Specifications Section 8 2...
Страница 418: ...395 Repeater Unit Section 10 2 Dimensions 42 3 50 3 1 27 5 95 mm...
Страница 419: ...396 Repeater Unit Section 10 2...
Страница 424: ...401 CX Integrator Section 11 1...
Страница 575: ...552 Current Consumption Summary Appendix D 552...
Страница 581: ...558 Index...
Страница 583: ...560 Revision History...