462
Temperature Input Unit Functions
Section 11-5
Setting the One-shot Time
1,2,3...
1.
Select the
Top/Valley
Tab Page and input the desired value in the
Shot Off
Delay
Field.
2.
Return to the
General
Tab Page, click the
Transfer [PC to Unit]
Button to
download the data, and then click the
Reset
Button to reset the Unit.
3.
Click the
OK
Button and exit the window.
11-5-5 Top/Valley Counter
The top/value count function counts the number of temperature tops or valleys
in devices or applications that have repetitive constant temperature rises (or
drops). A monitor value can be set for the counter to indicate when mainte-
nance is required for the Unit or sensor. The status can be read in the Monitor
Window or via an explicit message to know when the monitor value has been
exceeded.
Valley Counter Operation
The Valley Count function counts the number
of valleys in the temperature input value.
Temperature
input value
Hold value
Hold Flag
Hold function
starts.
Hold function
stops.
Valley hold
value
Last value
is held.
Содержание CRT1 - 10-2008
Страница 2: ...CRT1 Series CompoNet Slave Units and Repeater Unit Operation Manual Revised October 2008...
Страница 3: ...iv...
Страница 5: ...vi...
Страница 9: ...x...
Страница 15: ...xvi...
Страница 23: ...xxiv Conformance to EC Directives 6...
Страница 51: ...28 Slave Unit Models Section 1 2...
Страница 123: ...100 Connecting External I O for Slave Units Section 3 6...
Страница 365: ...342 Temperature Input Units Section 7 5...
Страница 381: ...358 Expansion Unit Specifications Section 8 2...
Страница 418: ...395 Repeater Unit Section 10 2 Dimensions 42 3 50 3 1 27 5 95 mm...
Страница 419: ...396 Repeater Unit Section 10 2...
Страница 424: ...401 CX Integrator Section 11 1...
Страница 575: ...552 Current Consumption Summary Appendix D 552...
Страница 581: ...558 Index...
Страница 583: ...560 Revision History...