6 Commissioning
Maschinenfabrik Reinhausen GmbH 2019
90
5163667/06 EN
ETOS
®
IM
4. Restart the device to apply the changed language setting.
6.3 Setting date and time
You can set the date and time in the following ways:
▪ Manually
▪ Time synchronization via control system (SCADA)
▪ Time synchronization via SNTP time server
If you are using a control system, the device automatically synchronizes the
date and time with the control system. If you would like to use an SNTP time
server, you must set the required parameters.
When doing so, observe the information provided in the Time synchroniza-
tion [
Section 7.25, Page 292] section.
6.4 Commissioning wizard
If you want the device to help when setting the relevant parameters, you can
use the commissioning wizard. The commissioning wizard provides a selec-
tion of parameters that you can configure in order.
A detailed description of each of the parameters can be found in the Opera-
tion [
To call up the commissioning wizard, you will need the necessary access
rights [
When in delivery status, you can log in as the administrator as follows:
▪ User name:
admin
▪ Password:
admin
To set the parameters with the help of the commissioning wizard, proceed
as follows:
1. Log in as a user with the necessary access rights.